Datakom DPR-145 User Manual Download Page 13

DPR-145 User Manual                                                                           V-3.0 

(14.09.2016) 

 

-13- 

 

 

 

TUŞ 

İŞLEM 

EKRAN 

 

 

The parameter to be modified is 
selected with MODE button.

 

 

When the parameter name is on 
display, hold the MENU button 
pressed during 5 seconds. The 
parameter value will be displayed.  

 

 

Adjust the parameter using up/down 
arrow buttons. 

In order to increase/decrease faster 
you can hold arrow buttons pressed. 

 

 

When MODE button is pressed, the 
parameter value is recorded and the 
next parameter name is displayed. 

 

 

 

DISPLAY 

DESCRIPTION 

MIN 

MAX 

 

PT100 CABLE SECTION (



PT100 cable section in mm

2

The factory set value is 0.5mm

2

.

 

0.10 

9.99 

 

PT100 CABLE LENGTH (



PT100 cable length in meters (m).  
The factory set value is 0m.

 

999 

 

TRIP RELAY TEST (



Used to test the TRIP relay. The value of  
“1” activates the relay. The value of “0” 
deactivates it.

 

 
 

 

5.4 MODIFYING PROGRAM PARAMETERS

 

5.5 PROGRAM PARAMETER LIST 

 

Summary of Contents for DPR-145

Page 1: ...6A FAN provides cooler fan control TRIP high temperature failure relay ALARM pre alarm relay FAULT sensor or internal failure indicator The unit offers an automatic self test feature The self test co...

Page 2: ...ranty voids if the unit is open Fuse must be connected to the power supply input Fuses must be of fast type with a maximum rating of 6A Disconnect all power before working on equipment When the unit i...

Page 3: ...FUNCTIONS 3 DISPLAYS 3 1 MODES OF OPERATION 4 ALARMS 4 1 ALARM MENU 5 PROGRAMMING 5 1 ENTERING THE PROGRAM MODE 5 2 LAMP TEST 5 3 RELAY TEST 5 4 MODIFYING PROGRAM PARAMETERS 5 5 PROGRAM PARAMETER LIST...

Page 4: ...ning Make electrical connections with plugs removed from sockets then place plugs to their sockets Otherwise sockets may get damaged Make sure not overloading relay outputs Use additional contactors i...

Page 5: ...DPR 145 User Manual V 3 0 14 09 2016 5 Panel Cutout Required Panel Depth 1 1 FRONT REAR PANELS 1 2 MECHANICAL INSTALLATION...

Page 6: ...ower supply input in close proximity of the unit Fuses must be of fast type with a maximum rating of 6A Use cables of appropriate temperature range Use adequate cable section at least 0 75mm2 AWG18 Fo...

Page 7: ...previous channel or increase related value program mode Switch to the next channel or decrease related value program mode IF HELD PRESSED DURING 5 SEC will be displayed and all Trip Fault and Alalrm...

Page 8: ...side 1 2 3 4 indicate the related channel number SCAN Displays channel temperatures switches to the next channel every 5 seconds AUTO Displays the temperature of the highest channel MAN Displays the t...

Page 9: ...will turn off and normal operating mode will be resumed ALARM CODE DESCRIPTION SHORT CIRCUIT Indicates a short circuit on the related channel The FAULT led and the related channel led turns on Cables...

Page 10: ...will turn on The alarm code will be displayed Different alarm types fault trip alarm may be scrolled with the MODE pushbutton If the related type of alarm has not occurred on any channel then wil be d...

Page 11: ...onds PGM will be displayed Every depression to the MODE button will switch to the next parameter Related parameter name is displayed When the name of the parameter to be modified is displayed hold pre...

Page 12: ...the screen Arrow down button deactivates the relay output and displays 0 on the screen Mode button will switch to next relay or parameter display 5 2 LAMP TEST When exiting the PROGRAM mode the unit m...

Page 13: ...ster you can hold arrow buttons pressed When MODE button is pressed the parameter value is recorded and the next parameter name is displayed DISPLAY DESCRIPTION MIN MAX PT100 CABLE SECTION PT100 cable...

Page 14: ...he relay The value of 0 deactivates it 0 1 ALARM PARAMETER Adjusts High Temperature Alarm limit values of each channel 0 295 TRIP PARAMETER Adjusts High Temperature Trip values of channels 5 300 FAN C...

Page 15: ...600 baud 7 56000 baud 3 14400 baud 8 57600 baud 4 19200 baud 9 115200 baud 0 9 MODBUS NODE ADDRESS nod This parameter defines the address of the unit in a Modbus network Each device in the same networ...

Page 16: ...tructure contain multiple registers Detailed description about the MODBUS protocol is found in the document Modicon Modbus Protocol Reference Guide This document may be downloaded at www modbus org do...

Page 17: ...4 Channel 4 Trip temperature C 16 BIT R W unsigned word 1 8 Fan Channel Fan relay channel selection 16 BIT R W unsigned word 1 9 Fan ON Fan Turn On Temperature C 16 BIT R W unsigned word 1 10 Fan OFF...

Page 18: ...3 registers ADDRESS BIT R W DESCRIPTION 20488 0 R O Alarm Relay Status 1 R O Trip Relay Status 2 R O Fan Relay Status 3 R O Fault Relay Status 4 15 R O Not used 20489 0 R O Channel 1 Alarm 1 R O Chan...

Page 19: ...Measuring Inputs 4 x PT100 3 terminals Accuracy 1 1 digit Measurement Range 40 to 250 C Power Consumption 4 VA Relay Outputs 5A 250V AC Serial Port Signal type RS 485 Protocol Modbus RTU Data Rate 240...