DKM-046 User Manual V-1.0
7
Although the unit is protected against electromagnetic disturbance, excessive disturbance
can affect the operation, measurement precision and data communication quality.
ALWAYS remove plug connectors when inserting wires with a screwdriver.
Fuses must be connected to the power supply inputs, in close proximity of the unit.
Fuses must be of fast type with a maximum rating of 6A.
Use cables of appropriate temperature range.
Use adequate cable section, at least 0.75mm
2
(AWG18).
Follow national rules for electrical installation.
Do not install the unit close to high electromagnetic
noise emitting devices like contactors, high current
busbars, switchmode power supplies and the like.
1.2 ELECTRICAL INSTALLATION