BUTTON  FUNCTION 

 

Genset runs off load. 

 

If the mains fail, then the genset runs 
and takes the load. 

 

Genset stops. 
If held pressed during 10 seconds, 
resets service counters. 

 

Selects next display value. If held 
pressed then selects first LAMP TEST 
the programming mode.  

 

If these two buttons are held pressed 
for 5 seconds, enters the special 
programming mode where high 
priority parameters are also 
programmable. 

 

SERVICE RESET: 

To turn off the SERVICE REQUEST led, and reset the 
service period, press the STOP key for 10 seconds. 
When “Srv” is displayed, service timers are reset and 
the service request is erased. 

 

 

MODE LEDS:

  Turns on when related mode is 

selected on the unit. 

STOP:

  In  this  mode,  if  mains  phase  voltages  are 

within the programmed limits then the mains contactor 
will be energized. The engine does not run. 

AUTO:

 If at least one of the mains phase voltages is 

outside limits, the mains contactor will be deactivated. 
The  engine  will  run.  When  alternator  phase  voltages 
and  frequency  are  within  limits,  then  the  generator 
contactor will be energized. 
When  all  the  mains  phase  voltages  are  within  the 
limits,  the  generator  contactor  is  deactivated  and  the 
mains  contactor  will  be  energized  and  the  diesel  will 
stop. The unit will be ready for the next mains failure. 

RUN:

 The operation of the generator is similar to the 

AUTO  mode,  but  the  mains  contactor  will  not  be 
deactivated and the genset will run off load.  

 

MAINS AND GENSET LEDS: 

MAINS:

 If mains phase voltages and frequency is 

within limits then this led flashes. When the load is 
on mains, this led turns on steady. 

GENSET:

 If genset phase voltages and frequency is 

within limits then this led flashes. When the load is 
on genset, this led turns on steady. 

 

PUSHBUTTON FUNCTIONS

 

RUN mode 
button 

STOP mode 
button 

AUTO mode 
button 

Menu 
selection 
button 

Display unit 
leds 

Display unit 
leds 

Mains led. 
Flashes when 
mains is OK, 
turns-on steady 
when load is fed 
by mains. 

Genset led. 
Flashes when 
genset is 
running, turns-on 
steady when 
load is fed by the 
genset. 

Summary of Contents for DKG-225

Page 1: ...rify correct terminal connections before applying power Only for front panel mounting Before installation Read the user manual carefully determine the correct connection diagram Remove all connectors and mounting brackets from the unit then pass the unit through the mounting opening Put mounting brackets and tighten Do not tighten too much this can brake the enclosure Make electrical connections w...

Page 2: ...Current Inputs CT inputs xxx 5A opt xxx 0 1A Analog Input Range 0 5000 ohms Digital Inputs 0 to 36V DC Operating temp 40 C 40 F to 70 C 158 F Storage temp 55 C 67 F to 80 C 176 F Maximum humidity 95 non condensing Dimensions 133x 107 x 46 mm WxHxD Panel Cutout 117 x 87mm minimum Weight 200 g approx Enclosure Flame retardant high temp ABS PC UL94 V0 IP Protection IP65 front with gasket IP30 rear EU...

Page 3: ... be deactivated The engine will run When alternator phase voltages and frequency are within limits then the generator contactor will be energized When all the mains phase voltages are within the limits the generator contactor is deactivated and the mains contactor will be energized and the diesel will stop The unit will be ready for the next mains failure RUN The operation of the generator is simi...

Page 4: ... period defined in Overload Timeout then a Overcurrent Load Dump alarm will be generated If this parameter is 0 then Overcurrent check is disabled P_05 Excess power limit kW 0 If the active power goes above this limit during the period defined in Overload Timeout then an Excess Power Load Dump alarm will be generated If this parameter is 0 then Excess Power check is disabled P_06 Overcurrent Exces...

Reviews: