background image

  

 

DKG-225, is a low cost AMF controller for 12V-DC 
gensets, featuring an internal battery charger. Internal 
fuel and crank relays are rated at 40Amps@12V-DC 
and do not require external relays. 

Thus a typical transfer panel will simply consist on 
one DKG-225 and two contactors, reducing material 
cost, panel size and production time.  

The unit supports also current transformer 
connections allowing detailed power measurements 
from both mains and genset sides. The standard unit 
supports 1A and 5A secondary CTs. A special version 
supports low cost and small 0.1A secondary CTs 
allowing more compact panel design. 

The 1Amp @12V-DC rated battery charger is 
sufficient for the float charging of the engine start 
battery. 

 

 

 Electrical equipment should be installed only by 

qualified specialist. No responsibility is assured by 
the manufacturer or any of its subsidiaries for any 
consequences resulting from the non-compliance to 
these instructions. 

 Check the unit for cracks and damages due to 

transportation. Do not install damaged equipment. 

 Do not open the unit. There is no serviceable parts 

inside. 

 Fuses of fast type with a maximum rating of 6A  

must be connected to phase voltage inputs in close 
proximity of the unit. 

 Disconnect all power before working on equipment. 

 When the unit is connected to the network do not 

touch terminals. 

 Any electrical parameter applied to the device must 

be in the range specified in the user manual. Values 
exceeding limits may shorten device life, destroy its 
precision or damage it. 

 Do not try to clean the device with solvent or the 

like. Only clean with a dump cloth. 

 Do not allow water to come in the unit. 

 Verify correct terminal connections before applying 

power. 

 Only for front panel mounting. 

 

 

Before installation: 

 Read the user manual carefully, determine the 

correct connection diagram. 

 Remove all connectors and mounting brackets from 

the unit, then pass the unit through the mounting 
opening. 

 Put mounting brackets and tighten. Do not tighten 

too much, this can brake the enclosure. 

 Make electrical connections with plugs removed 

from sockets, then place plugs to their sockets.

 

 Make sure that the ambient temperature does not 

exceed the maximum operating temperature limit.

 

 

During Installation: 

 Cables should be compatible with the operating 

temperature range. Use adequate cable section, at 
least 0.75mm

(AWG18).  

Below conditions may damage the device: 

 Incorrect connections. 

 Incorrect battery voltage. 

 Reverse battery voltage 

 Voltage at terminals beyond specified range. 

 Voltage applied to digital inputs over specified 

range. 

 Current at terminals beyond specified range. 

 Overload or short circuit at relay outputs. 

 Excessive vibration, installation on vibrating parts. 

Below conditions may cause abnormal operation: 

 Battery voltage below minimum acceptable level. 

 Frequency out of specified limits 

 Missing grounding. 

 

 

 

Make electrical connections with 
plugs removed from sockets, 
otherwise the unit may get 
damaged. 

 

 

Engine body must be grounded for 
the correct operation of the unit. 
Otherwise faulty voltage and 
frequency measurements may 
occur.

 

 

 

Do not install the unit close to 
high electromagnetic noise 
emitting devices like contactors, 
high current busbars, switchmode 
power supplies and the like. 

 

DKG-225 

GENSET CONTROL & ATS PANEL 

INSTALLATION GUIDE

 

 

 

Current Transformers must be 
used for current measurement.  

No direct connection allowed. 

 

INSTALLATION

 

 

SAFETY NOTICE 
Failure to follow below 
instructions may result in 
death or serious injury 

 

SAFETY FIRST !

 

Summary of Contents for DKG-225

Page 1: ...rify correct terminal connections before applying power Only for front panel mounting Before installation Read the user manual carefully determine the correct connection diagram Remove all connectors and mounting brackets from the unit then pass the unit through the mounting opening Put mounting brackets and tighten Do not tighten too much this can brake the enclosure Make electrical connections w...

Page 2: ...Current Inputs CT inputs xxx 5A opt xxx 0 1A Analog Input Range 0 5000 ohms Digital Inputs 0 to 36V DC Operating temp 40 C 40 F to 70 C 158 F Storage temp 55 C 67 F to 80 C 176 F Maximum humidity 95 non condensing Dimensions 133x 107 x 46 mm WxHxD Panel Cutout 117 x 87mm minimum Weight 200 g approx Enclosure Flame retardant high temp ABS PC UL94 V0 IP Protection IP65 front with gasket IP30 rear EU...

Page 3: ... be deactivated The engine will run When alternator phase voltages and frequency are within limits then the generator contactor will be energized When all the mains phase voltages are within the limits the generator contactor is deactivated and the mains contactor will be energized and the diesel will stop The unit will be ready for the next mains failure RUN The operation of the generator is simi...

Page 4: ... period defined in Overload Timeout then a Overcurrent Load Dump alarm will be generated If this parameter is 0 then Overcurrent check is disabled P_05 Excess power limit kW 0 If the active power goes above this limit during the period defined in Overload Timeout then an Excess Power Load Dump alarm will be generated If this parameter is 0 then Excess Power check is disabled P_06 Overcurrent Exces...

Reviews: