background image

 

 

 

 

 

 

 

 
DC SUPPLY:

 12 or 24 volts DC, (+) and (-) terminals. 

R-S-T:

 Mains phase voltages. 

MN:

 Mains neutral terminal. 

G:

 Generator phase voltage. 

GN:

 Generator neutral terminal. 

 

 

 
MAINS CONTACTOR:

 Normally closed relay output 

connecting the phase-R voltage to the terminal. 
(10amps@250V-AC) 

GENERATOR CONTACTOR:

 Normally open relay 

output connecting the phase-G voltage to the terminal. 
(10amps@250V-AC) 

REMOTE START:

 Normally open engine start request 

relay output. Connects the battery positive voltage to 
the terminal. (10amps@28V-DC) 
 
 
 
 
 

 

 
Alternator Voltage: 

300 V-AC max. 

Mains voltages:

 300 V-AC max (Ph-N) 

DC Supply Range:

 8 to 33 V-DC. 

Current consumption:

 80mA max. (outputs open). 

Wait Before Remote Start

: 3 sec. 

Engine Heating Period:

 5 sec. 

Generator Contactor Delay:

 0.75 sec. 

Mains Return Delay

: 30 sec. 

Mains Contactor Delay:

 0.75 sec. 

Low Voltage Limit:

 Adjustable from 70 to 270V-AC. 

High Voltage Limit:

 320 V-AC Ph-N (fixed) 

Operating temp.:

 -20

C (-4

F) to 70 

C (158

F). 

Storage temp.:

    -30

C (-22

F) to 80 

C (176

F). 

Maximum humidity:

 95% non-condensing. 

Dimensions:

 72x72x38mm (WxHxD) 

Panel cutout dimensions:

 68x68 mm 

Weight:

 140g (approx.) 

Installation:

 Front panel mounted. Retaining steel 

spring provided. 

        DATAKOM Electronics Ltd.                                           

Tel: +90-216-466 84 60   Fax: +90-216-364 65 65   e-mail: [email protected]   http: www.datakom.com.tr 

TECHNICAL SPECIFICATIONS

 

OUTPUTS

 

INPUTS

 

TYPICAL CONNECTION DIAGRAM 

 