DC SUPPLY:
12 or 24 volts DC, (+) and (-) terminals.
R-S-T:
Mains phase voltages.
MN:
Mains neutral terminal.
G:
Generator phase voltage.
GN:
Generator neutral terminal.
MAINS CONTACTOR:
Normally closed relay output
connecting the phase-R voltage to the terminal.
(10amps@250V-AC)
GENERATOR CONTACTOR:
Normally open relay
output connecting the phase-G voltage to the terminal.
(10amps@250V-AC)
REMOTE START:
Normally open engine start request
relay output. Connects the battery positive voltage to
the terminal. (10amps@28V-DC)
Alternator Voltage:
300 V-AC max.
Mains voltages:
300 V-AC max (Ph-N)
DC Supply Range:
8 to 33 V-DC.
Current consumption:
80mA max. (outputs open).
Wait Before Remote Start
: 3 sec.
Engine Heating Period:
5 sec.
Generator Contactor Delay:
0.75 sec.
Mains Return Delay
: 30 sec.
Mains Contactor Delay:
0.75 sec.
Low Voltage Limit:
Adjustable from 70 to 270V-AC.
High Voltage Limit:
320 V-AC Ph-N (fixed)
Operating temp.:
-20
C (-4
F) to 70
C (158
F).
Storage temp.:
-30
C (-22
F) to 80
C (176
F).
Maximum humidity:
95% non-condensing.
Dimensions:
72x72x38mm (WxHxD)
Panel cutout dimensions:
68x68 mm
Weight:
140g (approx.)
Installation:
Front panel mounted. Retaining steel
spring provided.
DATAKOM Electronics Ltd.
Tel: +90-216-466 84 60 Fax: +90-216-364 65 65 e-mail: [email protected] http: www.datakom.com.tr
TECHNICAL SPECIFICATIONS
OUTPUTS
INPUTS
TYPICAL CONNECTION DIAGRAM