background image

 

 

 

 

 

DKG-171 AUTO 

TRANSFER SWITCH 

INSTALLATION AND OPERATING INSTRUCTIONS

 

 

 

 

 

The  DKG-171  is  a  microprocessor  controlled  unit 
designed  to  monitor  the  3-phase  mains  voltages, 
send  remote  start  command  to  the  generating  set 
and make changeover of both generator and mains 
contactors.  

The front panel mimic diagram provides information 
about  mains  and  generator  power  availability  as 
well as contactor positions.  

The low limit of the mains and genset voltages may 
be manually adjusted via the potentiometer situated 
on  the  left  side  of  the  unit.  The  leftmost  position 
corresponds to 70 volts, the middle position to 170 
volts and the rightmost position to 270 volts-AC. 

 

The  DKG-171  continuously  monitors  the  AC mains 
phase  voltages.  If  at  least  one  of  the  phase 
voltages  goes  outside  set  limits,  it  initiates  a 
transfer cycle like below: 

-The green 

MAINS

 led turns to 

red

-The  unit  deenergizes  the  mains  contactor  output 
and the green 

LOAD MAINS

 led is extinguished. 

-After 

Wait  Before  Remote  Start  Delay,

  the 

Remote  Start

  output  is  energized.  The  generator 

remote  start  unit  receives  this  signal  and  runs  the 
engine. 
-When  the  generator  phase  voltage  is  within  set 
limits,  the  yellow 

GENSET

  led  will  illuminate  and 

the  unit  will  allow  the  genset  to  run  without  load 
during the 

Engine Heating Period

-When  the 

Engine  Heating  Period

  is  elapsed, the 

yellow 

LOAD  GENSET

  led  will  start  blinking  and 

the  unit  will  wait  for  the 

Generator  Contactor 

Delay

-At the end of the 

Generator Contactor Delay,

 the 

generator  contactor  output  will  be  energized  and 
the  yellow 

LOAD  GENSET

  led  will  illuminate 

steadily. 
-When  all  mains  phase  voltages  are  within  limits, 
the 

MAINS

  led will turn to green and the unit waits 

for 

Mains Return Delay

 for stabilization. 

-At  the  end  of  the  Mains  Return  Delay,  the  yellow 

LOAD  GENSET

  led  is  extinguished,  the  generator 

contactor  output  is  deenergized  and  the  green 

LOAD  MAINS

  led  will  start  blinking.  The  unit  will 

wait for 

Mains Contactor Delay

-At the end of the Mains Contactor Delay the green 
LOAD MAINS led will illuminate steadily,  the mains 
contactor output is energized and the 

Remote Start

 

output is deenergized. The unit will wait ready for a 
new mains failure sequence. 

The  DKG-171  provides  a 

TEST 

mode  pushbutton 

allowing  the  genset  to  be  tested  without  a  mains 
failure.  

In  TEST  mode,  the  Remote  Start  output  will  be 
energized  but  no  load  transfer  will  take  place 
unless  the  occurrence  of  a  mains  failure.  If  the 
mains fail, the load will be transferred to the genset. 
When  the  mains  voltages  are  within  limits the load 
will  be  transferred  to  the  mains, but the genset will 
be  kept  running.  It  will  only  stop  if  the  TEST  mode 
is cancelled. 

OPERATION

 

DESCRIPTION

 

Reviews: