DKG-105 User Manual V-17
- 3 -
To enter the program mode, first press the OFF button, then the MENU button and hold the two
buttons pressed for 4 seconds. The display shows (Pr) when program mode is selected.
PGM
NUMBER
PROGRAM OPTION
UNIT
FACT
SET
MIN.
VAL.
MAX.
VAL.
P01
Mains Voltage Lower Limit
Volt
170
30
250
P02
Mains Voltage Upper Limit
Volt
270
100
400
P03
Generator Voltage Lower Limit
Volt
180
30
250
P04
Generator Voltage Upper Limit
Volt
270
100
400
P05
Frequency Lower Limit
Hz.
45
10
60
P06
Frequency Upper Limit
Hz.
57
50
100
P07
Frequency Delay Timer
Sec.
2
0
15
P08
Number of Start Attempts
-
3
1
6
P09
Wait before Start Timer
Sec.
2
0
240
P10
Wait between Starts Timer
Sec.
10
2
30
P11
Start Timer
Sec.
10
2
15
P12
Stop Timer
Sec.
0
0
60
P13
Mains Waiting Timer
Min.
0.5
0
15
P14
Cooling Timer
Min.
1.5
0
15
P15
Mains Contactor Timer
Sec.
1
0
15
P16
Generator Contactor Timer
Sec.
4
0
240
P17
Relay and Oil Pressure
Configuration
-
0
0
15
P18
Wait Before Fuel Timer
Min.
0
0
240
P19
Emergency Stop/Remote Start
-
0
0
1
P20
Max Engine Run Time Limit
Hour
0
0
18
P21
Choke Relay Timer
Sec.
3.0
0.5
90
P22
Gas Engine Fuel Solenoid Delay
Sec.
0.0
0.5
20
P23
Reserved
-
0
0
255
H01
Engine Run Hours Digit 1
-
0
0
9
H02
Engine Run Hours Digit 2
-
0
0
9
H03
Engine Run Hours Digit 3
-
0
0
9
H04
Engine Run Hours Digit 4
-
0
0
9
H05
Engine Run Hours Digit 5
-
0
0
9
1. PROGRAMMING SUMMARY