System Installation and Configuration
96-30051-001 Rev. D3
DDN SFA12K (SFA OS 2.3.1) Hardware Installation & Configuration Guide | 26
❖
In the
Voltage Transfer Range
field, select “Wide”
❖
In the
Sensitivity
field, select “Low”
❖
In the
Line VRMS
field, enter the nominal AC line voltage value determined in
step
above
❖
In the
Wide VRMS Limit
field, enter “30”
❖
Click
Apply
to save the changes
5.
Select preferred source:
❖
Go to
Unit
tab
❖
Select
Configuration
-
source
❖
In the
Preferred Source
field, select “None”
❖
Click
Apply
to save the changes
6.
Verify that the Input A and B LEDs are both illuminated on the front panel
.
7.
Repeat steps
to
above on the other ATS.
8.3
Other Recommended Configurations
You may configure the date and time, administrator user name and password, and event
notifications for the ATS. Refer to the
SFA OS User Guide
(SFA12K ATS Recommended
Configurations) for more information.
Figure 18. Select Preferred Source
Figure 19. ATS Front Panel
Input LEDs