INSTALLATION

 

1.  UNPACKING and HANDLING 

 

Each unit is shipped assembled and factory tested. 
 
Ensure that all accessories are removed from the container before discarding packing material 
 
 

2.  MECHANICAL INSPECTION 
 

Inspect the front and rear of the equipment for shipping damage. Make sure the equipment is 
clean,  and  no  connectors  are  broken,  damaged,  or  loose.    If  equipment  appears  to  be 
damaged  or  defective  please  contact  your  distributor  or  Datatronix  at  1-610-429-1511  for 
assistance. 

 
 

 

 

3.  INSTALLATION and CONNECTIONS 

 

a.  AWG 22-24 Category 6 cable wires are recommended for this unit. 

b.  This patch panel supports T568A and T568B wiring configurations. Verify the wiring 

configuration conforms to the wiring color scheme depicted on the back panel cover. 

c.  Use the proper termination tools such as a 110 Impact Tool 

or Krone Impact Tool. 

d.  Using  the  supplied  screws  the  patch  panel  should  be 

installed  in  any  standard  19”  equipment  rack  or 
communications cabinet.  

 

e.  Remove 3” of jacket insulation and center spline from the cable. Leave no more than 

8mm or 0.3 inch of wire to make the connection to the IDC slots. 

 

f.  Locate the jacketed cable above the IDCs.  

 

 

 

g.  Using the wiring color scheme displayed on the back panel, 

terminate  each  cable  pair  in  its  color  slot.  Ensure  the  solid 
colored wire of each pair is placed in the correct slot. Use a 
110 or Krone Impact Tool to impact the wire into the 110IDC. 

 

 

h.  Place the IDC cover over the connections to reduce the 

presence  of  dirt  and  moisture  on  the  connections  in 
addition to better securing the wires. 

 

 