Voltage & Current Inputs
Ranges
±100mV, ±10V DC and ±20mA DC.
Input Impedance (Ohms)
>500M
Ω
, >1M
Ω
and <5
Ω
.
Sensor Excitation Supply (Tracker 321 and 332 only)
2-wire loop supply
24V DC nominally @ 35mA max.
Bridge supply
10V DC regulated @ 35mA max.
Isolation
functional isolation only.
Thermocouple Measurement
Resistance Thermometers
Configuration
2 or 3 wire.
Communications Interface
Isolation
500V DC/peak AC.
Type
RS485 2-wire multidrop.
Protocols
MODBUS RTU & ASCII, DTPI (ASCII)
Analogue Output
Isolation
500V DC/peak AC.
Output
Selectable 0 to 10V, 0 to 20mA or 4 to 20mA.
Maximum current output
22mA @ 18V.
Maximum voltage output
11V @ 22mA.
Maximum load (mA output) 900 Ohms.
Logic Outputs (Tracker 331 only)
Relay type
1 x normally open contacts. (Optionally 2.)
Rating
1A @ 230V AC, 1A @ 30V DC.
Relay isolation
Isolated from each other and all other inputs
and outputs.
SSR drive output
18V DC 20mA nominal
(see also Tracker 340 Logic Module).
Partial Load Failure Feedback
4 to 20mA or 0 to 10V DC input from an external current transmitter. The
CT signal must be a different signal type from the PV signal.
Packing List
The following items are included in the package with the instrument.
Mini CD (80 mm diameter) The CD contains the Reference Manual in PDF
format, foreign language Installation Guides
in PDF format, the instrument configuration
software and additional freeware utilities.
Installation Guide
Folded A3 Installation Guide detailing safety
and connection information.
Tracker 340 Expansion Module
1. Introduction
The Tracker 340 expansion module is connected to a Tracker 300 series
instrument via the expansion port. The Tracker 340 is powered by and
configured via the Tracker 300.
2. Connections
The diagram below shows the terminal connection arrangement.
Relay Connections
Logic Connections
3. Connecting the Status Inputs
There are two status (logic) inputs provided on the Tracker 340 expansion
module. The inputs can be used with either voltage free contacts, such as
relay contacts, switches, open collector transitor outputs, or voltage driven.
The inputs are active low, i.e. apply a short circuit between the status input
and status common. The following diagrams illustrate typical applications.
Status Input 1
Status Input 2
Voltage Free
Contacts
Open Collector
TTL Outputs
Voltage Driven
Note: 0V is active
4. Indicators
There are six LEDs on the front panel of the instrument, two green (input)
and four red (output).
Green LED Status Inputs 1 & 2– lit when the respective status input is
active.
Red LED 1, 2, 3 and 4
– programmable LEDs.
5. Specification
Relay Option
Relays
4 off, change over
Rating
1A @ 230V AC, 1A @ 30V DC
Relay isolation
Isolated from each other and all other inputs
and outputs
TTL Logic Option
Drivers
4 off, TTL
Rating
±20mA, source or sink
Isolation
No isolation
Status Inputs (both options)
Logic inputs
2 off, voltage free or TTL
Protection
Reverse diode protected
D
ATA
T
RACK
Process Instruments Ltd
153 Somerford Road
Christchurch, Dorset BH23 3TY
United Kingdom
TRACKER 300 SERIES
INSTALLATION GUIDE
DATA TRACK
PROCESS INSTRUMENTS
Accuracy Including Linearisation
Thermocouple
Range (
o
C) Worst Case
Typical @ 20°C
Type B, Pt30%Rh/Pt6%Rh
0 to 1820
±1.0°C
±0.5°C
Type J, Fe/NiCu
-210 to 1200
±1.0°C
±0.5°C
Type K, NiCh/Ni/Al
-270 to 1372
±1.0°C
±0.5°C
Type T, Cu/CuNi
-270 to 400
±1.0°C
±0.5°C
Type N, Nicrosil-Nisil
-200 to 1300
±1.0°C
±0.5°C
Type R, Pt13%Rh-Pt
-50 to 1767
±2.0°C
±1.2°C
Type S, Pt10%Rh-Pt
-50 to 1767
±2.0°C
±1.2°C
Accuracy Including Linearisation
RTD Type
Range (
o
C)
Worst Case
Typical @ 20°C
Pt100 (alpha = 385)
-200 to 850
±0.8°C
±0.4°C
Pt100 (alpha = 392)
-270 to 457
±0.8°C
±0.4°C
1
2
3
4
5
7
6
8
9
10
11
12
13
15
14
16
C
NO
NC
NC
NO
C
NC
NO
C
C
NO
NC
Relay1
Relay2
Relay3
Relay4
C - Common
NO - Normally Open
NC - Normally Closed
0V
O/P
Logic1
Logic2
Logic3
Logic4
O/P
0V
O/P
0V
0V
O/P
0V
0V
5V
0V
0V
5V