background image

DP10 CONTROL

 SERIES

P.O. Box 10

5000 W. 106th Street

Zionsville, Indiana 46077

Phone (317) 873-5211

Fax (317) 873-1105

www.dartcontrols.com

Instruction Manual

Signal Conditioner/Generator

LT168 (0318)

CONTROLS

A-5-4023E

Summary of Contents for DP10

Page 1: ... CONTROL SERIES P O Box 10 5000 W 106th Street Zionsville Indiana 46077 Phone 317 873 5211 Fax 317 873 1105 www dartcontrols com Instruction Manual Signal Conditioner Generator LT168 0318 CONTROLS A 5 4023E ...

Page 2: ...Installation Diagrams 5 P3 Terminal Block Hook Up Diagram 5 P3 Terminal Block Descriptions 5 Basic Operating Information 6 Visual Reference 6 How to Change a Parameter s Value The Short Story 7 Operating the User Interface The Long Story 7 Device Configuration 8 Mode of Operation 8 Software Parameters 9 Parameter Descriptions 10 Troubleshooting 14 Technical Support Options 14 What s Special About ...

Page 3: ...ign offers long term stability in a variety of environments Dual Mode operation Signal Scaling or Signal Generation Works in either voltage or Current output modes PWM voltage 1kHz 100kHz Optional Universal power supply accepts supply voltages of 85 265VAC 50 60Hz without switches or jumper settings Transient voltage protection protects device in harsh industrial environments 1 8 DIN panel mount i...

Page 4: ... 0 900 lb 14 4 oz 408 22g Operating Temperature Range 10C to 45C 14F to 113F Operating Humidity Range 95 non condensing Line Input Voltage Any Voltage from 85 265 VAC Line Input Frequency Any Freq from 48 62 Hertz Voltage Signal Input 0 5 VDC Optional Higher Voltage Signal Output 0 1 5VDC MIN 0 1 20 VDC MAX 10mA MAX mA Signal Input 4 20mA mA Signal Output 4 20mA Display Range Default 0 100 0 Maxim...

Page 5: ...70 DP10 MICRO DRIVE SIGNAL CONDITIONER ENTER CONTROLS 4 000 4 000 140 x 2 0 885 GEN SCL SPL PANEL MOUNTING GASKET WITH THE ADHESIVE SIDE OF GASKET FACING THE CUSTOMER MOUNTING PANEL CUSTOMER MOUNTING PANEL HOLE CUT OUT FOR CONTROL HOUSING APPROXIMATELY 3 622 WIDE BY 1 770 HIGH DP10 CONTROL SUPPLIED WITH EACH CONTROL 1 GASKET 2 2 6 32 X 3 4 PANHEAD BLACK OXIDE STAINLESS SCREWS 3 2 6 NUT WITH LOCKWA...

Page 6: ...her device P3 6 24VDC SUPPLY A 24VDC supply output is provided to the user for sensor or other device P3 7 mA OUTPUT The negative connection for either Scaled or Generated mA current output signal P3 8 mA OUTPUT The Positive connection for either Scaled or Generated mA current output signal P3 9 IN1 Contact input for user configurable actions such as specified output and set point lock P3 10 IN2 C...

Page 7: ...isplay setting and the input Current or Voltage effects the 4 20mA output In Voltage output mode the Display setting the maximum level set by the potentiometer R9 adjustment and the input Current or Voltage effects the output Voltage level see appropriate sections for proper hardware and software setup Gen Generate mode is active and depending on jumper configuration either a current or voltage wi...

Page 8: ...utton down for three seconds Once in Parameter Selection Mode the far left of the display will be a P The right side of the display will indicate the currently selected parameter number for editing purposes Pressing the Up or Down button will increase or decrease the selected parameter number on the display Although the parameter numbers are in numerical order some numbers are skipped These skippe...

Page 9: ...nal high input voltage or PWM 2 JP3 Determines the Output Signal type Vdc or mA Current MUST be same type as JP4 3 JP4 Determines the Output Signal type Vdc or mA Current MUST be same type as JP3 The four jumper settings allow the DP10 to operate as 4 20mA Input Scaled 4 20mA or 0 1 20Vdc Output 0 5Vdc Input Scaled 4 20mA or 0 1 20Vdc Output No Input Generator 4 20mA or 0 1 20Vdc Output Note Both ...

Page 10: ...p 20 Display Value at Minimum Output 9999 9999 Display Units 0 21 Display Value at Maximum Output 9999 9999 Display Units 1000 25 Output Minimum 0 1000 1 10th Percent Units 0 26 Output Maximum 0 1000 1 10th Percent Units 1000 Input 1 IN1 Setup 30 IN1 Input Configuration 1 Output 0 When IN1 Low 2 Output 0 When IN1 High 3 Output Setpoint When IN1 Low 4 Output Setpoint When IN1 High 5 Output 100 When...

Page 11: ...its that are required to be displayed regardless of the display value For example with a Display Zero Blanking setting of 3 and a displayed value of 6 the display would show _006 Mode 1 ___X Always show at least 1 digit Mode 2 __XXAlways show at least 2 digits Mode 3 _XXX Always show at least 3 digits Mode 4 XXXX Always show all 4 digits Parameter 13 Decimal Point DP Position This selects the form...

Page 12: ...cimal point s position For example setting this parameter to 125 would set the lower display limit at 12 5 0 125 or 125 according to the other configuration parameters Parameter 21 Display Value at Maximum Output This parameter defines the upper end of the display range This is the value which limits how high the user is able to scroll the displayed value in Running Mode This parameter is set with...

Page 13: ...ow state or wired to the unit s common the DP10 will force its output to 100 Once the IN1 input returns to an electrically high 5V state or allowed to float disconnected the output will once again correspond to the display value Mode 6 Output 100 When IN1 High WhentheIN1inputisatanelectricallyhigh 5V stateorallowedtofloatdisconnected the DP10 will force its output to 100 Once the IN1 input returns...

Page 14: ...de 7 Lock Set Point when IN2 is High LOC is displayed when one of the front panel buttons is pressed with IN2 in an electrically High State Program by bringing IN2 terminal P3 10 to electrically Low state or wire to unit s Common terminal P3 11 Enter Program Mode Select Parameter 35 Press Enter select value item 7 Press Enter again Note Select a value 1 6 to Exit the LOCK Set Point than press ente...

Page 15: ...C displayed Parameter 30 or 35 is set to 7 Change input state of S1 or S2 or reprogram Parameter 30 or 35 Does not provide proper output Jumpers in wrong position Verify jumpers are properly set for desired operation see table page 7 No output if either JP3 or JP4 in wrong location JP1 in wrong location For Scaled Mode neither current nor voltage output will be properly scaled with the intended in...

Page 16: ... 317 873 1105 www dartcontrols com ISO9001 REGISTERED MADE IN USA productionandheadquarters facility with over 2 000 000 variable speed units in the field In addition to the standard off the shelf products you canselectfromawidevariety of options to customize controls for your specific application For further information and application assistance contactyourlocal Dart sales representative stockin...