Introduction

 

This specification is a technical document that certifies the DanVex AD-400 dehumidifier 
parameters and characteristics.

 

Purpose

 

DanVex AD-400 (in short  AD-400) is  designed  for  efficient  air  dehumidification  with  the  air 
humidity  up  to  100%,  at  the  temperature  from  –20

º

С  to  +40

º

С  with  minimum  energy 

consumption. It can be used either as an independent unit for installation inside and outside of 
premises where air humidity control is required or along with an air treatment system.

 

Design

 

The dehumidifier answers IP 44 protection class according to IEC.

 

Body

 

The dehumidifier body is made of stainless steel. The front part of the dehumidifier is equipped 
with  a  detachable  panel  that  assure  access  for  maintenance.  Air  ducts  are  connected  via 
standard size round air ducts. The electric panel is located in a separate section in the humidifier 
upper part, the control panel is located on the dehumidifier front part.

 

Rotor

 

The  dehumidifier  is  equipped  with  a  drying  rotor  manufactured  in  accordance  with  unique 
technologies covered by a patent in force. The rotor represents a matrix consisting of numerous 
air channels. It is made of composite material with introduced SelicaGel and assures a very 
large contact area with air flow for moisture adsorption in the small volume of the  rotor. This 
material is highly efficient for water molecules attraction and retention, it is noncombustible and 
explosion-proof, with a long service life. The rotor manufacturing technology assures production 
of a product capable of saturated air processing without risk of destruction, it means that the 
rotor can be used along with a precooler. Besides, the rotor will not be damaged even if the fan or 
the reactivation air heater fail to function.

 

Filters

 

The dehumidifier is equipped with two filters. One filter is located at the dehumidified air inlet, the 
another one is installed at the reactivation air inlet.

 

Air flow fans: for dehumidified air flow and for reactivation air flow

 

The fans are of a radial type, single phase, 

IP 54 class, ISO F. The fans maintenance can be 

performed after the service panels are removed.

 

Electric panel

 

Electrical components are located inside the dehumidifier and can be reached through the top 
panel. Switches and indicators are located in the front part of the electric panel.

 

Reactivation air heater

 

The reactivation air heater is of PTC (Positive Temperature Control) type, its overheating is 
impossible

.

 

Control panel

 

Different operation modes can be selected using the switches located in the front panel: 
0/OFF 

– 

The dehumidifier does not operate.

 

1/ON  – 

The dehumidifier is in operation mode.

 

MAN   – 

The dehumidifier operates in a continuous mode.

 

AUTO 

– 

Automatic mode at using an external humidistat or at connecting other 

external control devices.

 

Summary of Contents for AD-400

Page 1: ...DanVex AD 400 Adsorption air dehumidi er Operation manual...

Page 2: ...R www danvex...

Page 3: ...NT Safety instructions 3 Introduction 4 Purpose 4 Design 4 Operation principle 5 Dimensions and weight 5 Installation 6 Technical data 7 Commissioning 7 Maintenance 8 Transportation 8 Parts list 9 War...

Page 4: ......

Page 5: ...explosion hazard Before opening any panels of the unit body it is required to disconnect the dehumidi er from the mains Before starting any maintenance works the dehumidi er should be out of operatio...

Page 6: ...all volume of the rotor This material is highly ef cient for water molecules attraction and retention it is noncombustible and explosion proof with a long service life The rotor manufacturing technolo...

Page 7: ...ondition DRY AIR and is directed to a certain part of the building or a technological process where dehumidi ed air or a certain air humidity levels are required Since the rotor rotates slowly the inc...

Page 8: ...e rotor The rotor is reactivated by another air ow preheated to 120 C The moisture is removed from the room in the form of moist air Pic 1 Dehumidi er air ows diagram Pic 2 AD 400 dehumidi er dimensio...

Page 9: ...upright it should be insulated and drain holes should be drilled in the lowest part of the elbow bend 2 4 mm Regeneration airduct The regeneration air duct should be as short as possible A metal net...

Page 10: ...ls are clean and not blocked 4 Make sure that air lters are installed and clean 5 Manually turn the fans impellers and make sure they rotate freely 6 Check the internal fuse 7 Close the service panels...

Page 11: ...per month Never use the dehumidi er without lters Rotor The rotor is maintenance free However for cleaning purposes it can be ushed out by compressed air A rotor cleaning procedure requires special k...

Page 12: ...w danvex 1 0 Parts list Table 3 Name Number per dehumidi er Rotor drive motor 1 Condenser 1 Belt pulley 1 Rotor drive belt 1 Belt tensioner 1 Dehumidi ed air fan 1 Regeneration air fan 1 Heater 1 Roto...

Page 13: ...ns when it supplies the Customer a repaired or a spare part Parts repair or replacement does not resultin the warranty period extension The parts and components replaced under the warranty belong to D...

Page 14: ......

Reviews: