Preventive service
Introduction
The free cooling unit requires preventive maintenance at regular intervals in order to
avoid stoppages and impaired performance. It is important to bear in mind that the ser-
vicing interval may vary depending on the conditions of the environment in which the
cooler operates.
NB
Turn off all electrical power to the unit before carrying out any work on it.
Make sure that all work has been carried out correctly before turning the power back
on.
Service function
“Timer”
The control unit has a service function to provide a better work climate for 20 minutes
while service personnel are in the electronics cabinet. In order to activate the service
function, select one step up from the main menu to "Timer". The press "Enter". The unit
will then start to count down from 20 and then return to normal operation.
Servicing interval
Dantherm recommends that the unit is serviced at least once a year. It is also recom-
mended that the unit is thoroughly inspected during the initial service in order to de-
termine whether or not the servicing interval is too long. We recommend that preventive
maintenance is carried out during the spring.
Warranty require-
ments
The factory warranty only applies if servicing has been carried out and documented at
an interval of a maximum of one year. The documentation may take the form of a writ-
ten log.
Once you have fin-
ished
Before leaving the electronics cabin, make sure that the control unit has no alarms!
Recommended ser-
vice order
The recommended procedure for preventive maintenance is:
Step
Activity
1
Make sure that the power supply to the unit has been safely turned off.
2
Remove the old filter and carefully clean the unit.
3
Clean the dampers and check that they work and close tightly.
4
Clean the fan and check its attachment.
5
Check and clean the air intake and ventilation accessories.
6
Carefully fit the new filter.
7
Close the unit and ensure that all servicing has been carried out correctly.
8
Turn on the power to the unit.
9
Run the self-test in accordance with the separate control unit manual.
Function test
The function test for fan and filter alarms may be carried out as follows.
Function test
Activity
Filter
Open the service hatch and place a piece of cardboard or similar ma-
terial on the inlet side of the filter so that it blocks a large part of the
filter surface. Close the service hatch, start the free cooling unit and
check that a filter alarm is given. Turn off and remove the piece of
cardboard.
Fan
Open the control unit hatch and disconnect the yellow cable (ACUE)
(brown for TKS 3000) which is connected to "Tc1" (ACUE), ("TK1" for
TKS3000). Close the hatch, run the free cooling unit and check that a
fan alarm is given. Reset the control unit.
Summary of Contents for TKS 60
Page 1: ...1 087403 Version 1 1 01 06 2015 TKS 60 Service manual Rev 1 1 en se...
Page 9: ...7 087403 Version 1 1 01 06 2015 Mount filter 1 2 Fit sealing strips Continued overleaf 35 mm...
Page 10: ...8 Mount filter continued 3 3...
Page 15: ...13 087403 Version 1 1 01 06 2015 Electrical diagram 48 V DC ACUE 3000...
Page 16: ...14 Electrical diagram 230 V AC TKS 3000A EC...
Page 27: ...25 087403 Version 1 1 01 06 2015 Montera filter 1 2 Montera t tlister Continued overleaf 35 mm...
Page 28: ...26 Montera filter continued 3 3...
Page 33: ...31 087403 Version 1 1 01 06 2015 Elschema 48V DC ACUE 3000...