![Dantherm HEX 70 Service Manual Download Page 18](http://html1.mh-extra.com/html/dantherm/hex-70/hex-70_service-manual_3515867018.webp)
18
How to replace the external fan,
continued
Procedure,
continued,
continued
Step
Action
17
Fasten the cable with a cable binder
18
Fasten the fan suspension with four new screws with glue.
Important: Fasten with 1.5 Nm
19
Remount the two plugs for the controller
20
Remount the front cover
21
Remount the controller
22
Connect power
The test program runs through all functions.
Make sure the unit does not come out with an alarm signal.
In case of an alarm signal, please see please
on page 12.