Dantherm HCP 10 Installation And User Manual Download Page 6

 

088162 – Version 1.3 – 

021018 

Using the control panel, 

continued

 

 

 

 

Auto bypass  
cooling  
mode 
 

Only available if mechanical bypass damper is mounted inside the unit,                           
and enabled in the PC tool or via remote control (HCP 10). 

Automatic bypass cooling is dependent on user settings.                                 
On remote control (HCP 10) and PC tool the following is possible: 

 

Setting the minimum outside temperature within the range         
8-15°C.  

     Setting the  extract setpoint in which the bypass damper is opened. Range is      

             22-30°C, with the possiblety to select “off”  to disable the auto bypass. 

 

 

When the following is present the automatic bypass cooling will open. 

 

If outside air is 2°C lower than extract 

 

AND the outside is higher than set point. 

 

AND the extract is higher than set point. 

Bypass is closed again if outside or extract conditions is below setpoint.  
Bypass LED will light permanenly when damper is open 
 

 

 

Manual bypass  
mode 
 

Only available if mechanical bypass damper is mounted inside the unit, and 
enabled in the PC tool 
If the parameter for the auto bypass isent avalible, you can select manually 
bypass by presssing the bypass key once. This will override the setpoints, 
and activate bypass for 1 hour if the outside temperature is 2°C lower than 
inside. 

 The following parameter must be present for the manual bypass cooling to open:

 

 

Outside air < than supply air and extract 

 

Outside air > 9°C  

 

 

 

Extract > 15°C

 

Bypass LED will light when damper is open

 

 

 

Fireplace 
 

A fireplace needs overpressure inside the house in order to avoid smoke in 
the living room when lighting it up. Fireplace mode will: 

 

Put supply fan into speed 3 

 

Reduce the extract fan speed to 50% of supply, in order to create 
this overpressure. 

 

If supply air <9°C fireplace mode will be disabled 

If fireplace is enabled in PC tool the fireplace function can be activated by pressing the 
manual fan speed for 5 seconds. Fireplace function is automatically disabled after 7 
minutes, but can also be disabled manually by pushing MANUAL for 5 seconds again.  
Fan speed 3 LED´s will flash during the 7 minutes fireplace count down. 
 

Continued overleaf 

Summary of Contents for HCP 10

Page 1: ...1 088162 Version 1 3 021018 Remote Control HCP 10 Installation and User Manual Rev 1 3 en...

Page 2: ...sure that you have the HCP10 and a small screwdriver available before you start Connect the RJ11 cable to the Domestic Ventilation unit using the MODBUS connection 2 Connection Description 1 ETHERNET...

Page 3: ...all if not already done The HCP 10 fits to a GIRA EAN 4010337061038 or single LK Fuga EAN 5703302105002 green wallbox Unterputzdose 2 Mount the metal frame on the wallbox using the 2 screws 3 Put the...

Page 4: ...e 2 Supply Air Press and keep it pressed while you press to increase the speed of the supply fan Alternatively press to decrease the speed The speed of the supply air will be increased decreased 3 Exh...

Page 5: ...hes to indicated auto mode demand controlled by the VOC CO2sensors Demand mode In this mode Controlled by VOC and RH sensor accessory the unit will automatically adjust the ventilation level to comply...

Page 6: ...is mounted inside the unit and enabled in the PC tool If the parameter for the auto bypass isent avalible you can select manually bypass by presssing the bypass key once This will override the setpoin...

Page 7: ...eds to be changed Please see the service guide section in the Service Manual for the product to learn how to replace the filters Press the button once to mute for a period of time Press and hold for 1...

Page 8: ...er tages forbehold for trykfejl og ndringer Dantherm can accept no responsibility for possible errors and changes Irrt mer und nderungen vorbehalten Dantherm n assume aucune responsabilit pour erreurs...

Reviews: