INSTALLATION & SERVICE MANUAL FOR PROFESSIONALS
Installation
: Calibration of airflow
en
Step
Action
12
Write down the final set-ups for the pressure losses over the heat exchanger and air
flow rates in the table on the unit:
Deactivate Installation Mode by pressing Manual + Auto for 6 seconds.
The operational modes are described closely in the user’s guide.
Procedure,
continued
After balancing