25
Installation
: Initial calibration
en
5
Move the ΔPa meter across the
extract
air path as shown. This
example is based on the unit being
in operation
mode A
.
086374 -
Conne
ction - HCC
10092014
Rechtsversion(B)
Right unit
unità destra
Linksversion(A)
Left unit
unità sinistra
Tear her
e
Tear her
e
2
1
2
1
Remove if bypass is present
6
Adjust the
extract
fan speed, according the guide in the PC Tool on your computer .
The goal is to adjust the fan until the ΔPa meter shows the pressure drop value that was
read in point no 2,
deducted a few percent,
in order to create a small under pressure
inside the house.
7
Disconnect the ΔPa meter, as well as the computer. The unit is now ready for many
years operation.