
28
Description
Value
Off
temperature when fan stops
20
On
Temperature when Fan starts
23
Min °C
temperature at bottom of P-band
25
Max °C
Temperature at top of P-band
29
Set Point
The wanted indoor temperature; fan
speed will be adjusted between Min°C
and Max °C
27
A/C 1 on
External Air Con unit 1 start if connected
31
A/C 1 off
External Air Con unit 1 stops if connected
29
A/C 2 on
External Air Con unit 2 start if connected
33
A/C 2 off
External Air Con unit 2 stops if connected
31
Emergency on
Fan run 100% and both A/C 1 and A/C 2 starts
38
Emergency off
Fan stops both A/C 1 and A/C 2 continue to run
36
Energy save Mode
(Freecooling > A/C)
If outdoor temperature is less than 1°C colder than indoor room temperature the Flexibox
Fan will stop.
The connected Air-con units will start and stop according to the table above.
Summary of Contents for Flexibox 900
Page 1: ...1 Flexibox 900 Quick setup guide Rev 1 3 20 3 2017...
Page 5: ...5 1x 1x 1x 2x 1x Tools needed...
Page 10: ...10 Outdoor Air Flow Up Seal unit Flexibox 900 Outdoor...
Page 15: ...15 Outdoor Air Flow Down Mount unit Flexibox 900 Outdoor 4x 8 mm 4 mm 3 mm Seal unit...
Page 17: ...17 Indoor Dimensions...