11
Technical data DFC 350
Introduction
This Free Cooling unit is very compact, quiet and economic due to the Displacement
Free Cooling system. In this product the EC-fan signal is reduced to 5V to achieve the
optimized performance.
Air flow and sound
This table shows the technical data for airflow and sound pressure:
Parameter
48V DC
230V AC
Max air flow
514 m
3
/h
514 m
3
/h
Max air flow
143 l/s
143 l/s
Free cooling capacity at
Δ
t=5°C
3 kW
3 kW
Max power consumption
40 W
35 W
Sound pressure at 5m from shelter 36 dB(A)
34 dB(A)
Sound pressure at 10m from shelter 31 dB(A)
31 dB(A)
Cabinet
This table shows the specifications for the cabinet:
Specification
Designation
DFC 350
Weight
Controller included 10 kg
Metal sheet material
Aluzinc AZ150
0,8-1,5 mm
Fan motor
This table shows the data for the fan motor:
Voltage version
48V DC
230V AC
Voltage nominal
48V DC
230V AC
Current
2,3 A
0,9 A
Max power consumption at standard settings
40 Watt
35 Watt
Speed
1500 rpm
1450 rpm
Filter
This table shows the data for the filter:
Specification
Filter data
Type
Bag filter
Filter Class
M5
M6
Total Area
1,4 m
2
1,4 m
2
Recommended filter monitor settings
200 Pa
200 Pa
Summary of Contents for DFC-350-230V-C3-W-FG
Page 1: ...DFC 350 and 450 Service manual No 095821 rev 1 5 19 12 2019 EN...
Page 19: ...19 Wiring diagram CC3000...
Page 30: ...30...
Page 31: ...31...