3. INSTALLATION
12
3.3.2 Drop bridge
To avoid condensate leaving the unit through the module joint, a bridge must be mounted
between the two drip trays of the modules. This bridge is delivered separately and should be
mounted when the modules are in place.
•
Place a strip of sealing on the backside of the bridge (Detail C)
•
Turn over the bridge and place it between the two drip trays with the sealed side facing
the drop catcher.
•
If the sealing should not be enough to keep the bridge in place, it is possible to fasten
the two ends of the bridge to the module frame with two rived nuts (Detail B).
It is important that the drop bridge is installed and sealed correctly, to avoid uncontrollable
discharge of condensed water and water damage of the building!