8. APPENDIX
25
8. Appendix
8. Parameter settings FC 101
Parameter
Description
Value
Function / unit
Comment
1-00
Configuration
0
Process open loop
1-03
Torque characteristic
1
Variable torque medium
1-20
Motor power
*
kW
* See motor plate
1-22
Motor voltage
400
V
1-23
Motor frequency
50
Hz
1-24
Motor current
*
A
* See motor plate
1-25
Motor speed
*
rpm
* See motor plate
1-90
Motor protection
2
Thermistor trip
With thermistor
Motor protection
4
ETR Trip
No thermistor
1-93
Connection
6
Digital input 29
With thermistor
Connection
0
No thermistor
No thermistor
3-02
Minimum Reference
0
Hz
3-03
Maximum Reference
*
Hz
* Max motor frequency
3-41
Ramp up time
150
Sec
3-42
Ramp down time
100
Sec
4-12
Motor Speed low
15
Hz
4-14
Motor Speed high
*
Hz
* Max motor frequency
4-19
Max Output Frequency
*
Hz
* Max motor frequency
5-40
Relay output 1-3
9
Alarm
6-10
Low voltage
0
V
6-11
High voltage
10
V
6-15
Terminal 53 High Ref.
*
Hz
* Max motor frequency
6-19
Terminal 53 mode
1
V
** Thermistor connection at terminal 29 and 50
All other parameters are standard Danfoss factory settings.
Summary of Contents for DanX AF Series
Page 1: ...DanX Pool AF User Manual Rev 2 3 961405 en...
Page 28: ......
Page 29: ......
Page 30: ......