Alarm out
In order to create the correct functionality on any hardwired alarm/digital in connections, the
corresponding parameter, needs to be set up correct.
After connecting the wires to the output terminals, please enter the parameter setting
through the SD card. See more in section “SD card” on page 1111
Under the system, control configuration menu you will find these settings:
Alarm Mapping
1.Alarm1 2.Alarm2
1.Pwr Save Mode [PSM][0/1]:
1
0
2.Room Temp H/L [THL][0/1]:
1
0
3.Fan 1 [F1][0/1]:
1
0
4.Fan 2 [F2][0/1]:
0
0
5.Fan 3 [F3][0/1]:
0
0
6.Onbrd. Sens [OS][0/1]:
0
0
7.Room Sens [RS][0/1]:
1
0
8.Amb. Sens [AS][0/1]:
1
0
9.Supp. Sens [SS][0/1]:
0
0
10.Cond. Sens [CS][0/1]:
0
0
11.Digi.1 I/P [FIL][0/1]:
0
0
12.Digi.2 I/P [FI][0/1]:
0
0
13.Door Xtch I/P [DI][0/1]:
0
0
14.Filt Grd I/P [FI][0/1]:
0
1
15.Phase I/P [FI][0/1]:
0
0
In these default values above, its shown that:
•
The filter guard is routed to activate alarm 2 output
•
Selected other alarms are routed to alarm 1 output.
If any of the alarms need to be changed, please follow the for SD card usability guide in sec-
tion “SD card” on page 11
If the default “normally open” alarm state is to be changed to “normally closed”, please locate
and change the jumper illustrated in section “External connections” on page 17