14
3.2 Condensate outlet
The condensate outflow device is located at the right hand side of the unit. The unit is fitted with an outlet stub for
connection of a 32 mm permanent pipe installation, which is led to a floor drain or a container.
It is important that the water pipe has a fall away from the unit of at least 2%, otherwise the water will overflow in
the condensate tray.
4. Electrical connection
Introduce the power supply cable either through the top cover panel or the rear cover panel of the unit. Lead the
cable through the air outlet compartment down to the terminal strip located behind the right-hand control panel.
Connect it to the terminals L1, L2, L3, N and PE. Power is connected to the unit in accordance with the data plate.
Please refer to the wiring diagrams on page 39.
The terminal strip is located behind the control panel at the right hand side of the unit
4.1 Control panel indications
The control panels, located at the left side and the right side of the unit respectively, indicate the following
operation modes.
Caution:
Observe local power supply company
regulations!