6. Connect power.

Connect the power source (power off) to the display box:

Battery to the -48V pin through a one ampere fuse and ground

to the +48V pin.

7. Mount the display box.

Mount the display box before reinstalling the cover. Use the

mounting holes on the back or on the left side of the box. Use #

6 mounting hardware (not supplied).

Replace the cover on the display box.

8. Mount the switch box.

Remove the cover from the switch box and mount it, using the

mounting holes on the back  Use #6 mounting hardware (not

supplied).

Replace the cover on the switch box.

C

HECKOUT

To verify the operation of the 41071 Alarm Display Unit, follow

these steps.

1. Apply power to the unit. Make sure the ON/ACO switch on the

remote switch box is in the ON position.

2. Push the AUDIO-VISUAL TEST button on the remote switch

box.
In proper operation, the four lamps light, and the audible

alarm sounds. To adjust the volume of the audible alarm, turn

the screw on the right side of the alarm display box.

3. Cause an alarm on each input.

In proper operation, the appropriate lamp lights and the au-

dible alarm sounds.

4. To disable the audible alarm, put the ON/ACO switch in the

ACO position.
In proper operation, the audible alarm does not sound when an

alarm occurs.

L

AMP

 R

EPLACEMENT

 P

ROCEDURE

To replace the lamps on the 41071 Alarm Display Unit, follow the

procedure below:

INSTALLATION

N

OTE

:

The unit operates at -48 VDC.

For -24 VDC operation, contact

Dantel’s Field Service Depart-

ment.

Summary of Contents for B23-41071

Page 1: ...lete information on electrostatic discharge safety precautions refer to BellcoreTM Technical Reference TR NWT 000870 Copyright 1999 by Dantel Inc Dantel is a registered trademark of Dantel Inc ISO 900...

Page 2: ...e switch box is in the ON position You can change the alarm volume by adjusting a screw on the right side of the display box When the ON ACO switch is in the ACO Alarm Cut Off posi tion the audible al...

Page 3: ...ON ACO switch is in the ON position You can change the alarm volume by adjusting a screw on the right side of the display box When the ON ACO switch is in the ACO Alarm Cut Off position the audible al...

Page 4: ...4 41071 1199 90 00037 CIRCUIT DESCRIPTION FIG 1 SCHEMATIC 41071 ALARM DISPLAY UNIT ALARM INPUTS P W B A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18...

Page 5: ...and the switch box at floor level The 41071 Alarm Display Unit can be used with the following devices MULTIPLEALARM TRANSMITTERS MATS Inputs to the Alarm Display Unit can come from the A through D ala...

Page 6: ...Processor MAP To report all four alarm levels A B C D you need two SAAMs Refer to Fig 3 FIG 3 TYPICAL RELAY CONNECTIONS 46017 SUMMARY AUDIBLE ALARM MODULE SUMMARYALARMMODULE Dantel s 46019 Summary Ala...

Page 7: ...use this application you can connect the outputs of the CPMs to the Alarm Display Unit s inputs for alarm indication Refer to Fig 5 APPLICATION INFORMATION A 40 42 39 K1A K1B B 44 43 51 K2A K2B 9 5 K3...

Page 8: ...K2B K2A K1A K1B 48 VDC CONTROL OUTPUT 46028 AND 46029 CONTROL POINT MODULES 4 3 6 5 8 7 12 11 10 9 14 13 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 1 2 X 1 X 2 X 3 X 4 X 5 X 6 X 7 X 8 X 9 X 10 X...

Page 9: ...PICAL RELAY CONNECTIONS 46001 STATUS MONITOR APPLICATION INFORMATION GLOBAL VISUAL LOCAL VISUAL AUDIBLE 48 VDC K3B 48 VDC K3A 41071 ALARM DISPLAY UNIT K2B K2A K1A K1B 48 VDC 1C 1D 2E 2F 4A 4B MINOR AL...

Page 10: ...ire to pin 2 of SW1 White orange wire to pin 3 of SW1 White green wire to pin 4 of SW1 Green white wire to ground pin 48V White blue wire is not used To install the 41071 Alarm Display Unit refer to F...

Page 11: ...d middle PCBs Jumper the cathode non numbered side of these diodes to gether Wire one cathode to K2A on the bottom PCB Wire the ground outputs from the relays of the MATs SAAMs SAMs or CPMs that will...

Page 12: ...ay Unit follow these steps 1 Apply power to the unit Make sure the ON ACO switch on the remote switch box is in the ON position 2 Push the AUDIO VISUAL TEST button on the remote switch box In proper o...

Page 13: ...udible alarm are working push the AUDIO VISUAL TEST button on the remote switch box To enable the audible alarm put the ON ACO switch on the remote switch box in the ON position To disable the audible...

Page 14: ...n instrument signed by a duly authorized officer of the Seller and accepted by the Buyer Warranty and remedies on products not manufactured by the Seller are in accordance with warranty of the respect...

Reviews: