Configuring a responder port for DCPF protocol:
1.
Type 2 at the configuration screen to display the responder port
prompts.
2.
SELECT PORT NUMBER - Type the port number to be config-
ured. Valid entries are 1, 2, or 4.
For the following selections, type S or press ENTER to skip to the
next selection, type F to save changes and exit the port configura-
tion, or type Q to quit the port configuration without saving any
changes.
3.
SELECT PROTOCOL - Set for DCPF. Type 1 if the protocol is not
set for DCPF.
4.
SELECT BASE ADDRESS - Enter the base (first) address to which
the port will respond. Valid entries are 1-253. Refer to Fig. 9. If a
new address is entered, press the ENTER key.
5.
SELECT BAUD RATE - Enter the desired baud rate. Valid entries
are 1 = 300, 2 = 600, 3 = 1200, 4 = 2400, 5 = 4800, 6 = 9600. For port
4, the 202 modem port, the baud must be 1200.
6.
SELECT PARITY - Set for none. Type 1 if the parity is not set for
none.
7.
SELECT STOP BITS - Set for 1. Type 1 if the number of stop bits is
not set for 1. Changing the value, typing S or F, or pressing EN-
TER saves any changes and brings up the configuration screen.
8.
SELECT RTS/CTS HANDSHAKE - Default is 1 (OFF). Typing 2
enables RTS/CTS handshaking.
Configuring a responder port for DCP protocol:
1.
Type 2 at the configuration screen to display the responder port
prompts.
2.
SELECT PORT NUMBER - Type the port number to be config-
ured. Valid entries are 1, 2, or 4.
For the following selections, type S or press ENTER to skip to the
next selection, type F to save changes and exit the port configura-
tion, or type Q to quit the port configuration without saving any
changes.
3.
SELECT PROTOCOL - Set for DCP. Type 2 if the protocol is not
set for DCP.
4.
SELECT BASE ADDRESS - Enter the base (first) address to which
the port will respond. Valid entries are 1-253. Refer to Fig. 9. If a
new address is entered, press the ENTER key.
5.
SELECT BAUD RATE - Enter the desired baud rate. Valid entries
are 1 = 300, 2 = 600, 3 = 1200, 4 = 2400, 5 = 4800, 6 = 9600. For port
4, the 202 modem port, the baud must be 1200.
6.
SELECT PARITY - Set for none. Type 1 if the parity is not set for
none.
INSTALLATION