pressure valve, water filter, etc.). If all these 
are OK, the problem may be due to either 
refrigerant overcharging or the presence of 
a noncondensable (e.g. air, moisture) in the 
circuit.

 •  

The low-pressure switch trips out: Check 
evaporator operations (coil cleanliness, fan 
operations, water flow, water filter, etc.), liquid 
refrigerant flow and pressure drops (solenoid 
valve, filter dryer, expansion valve, etc.), 
refrigerant charge.

 •   Low refrigerant charge: The correct refrigerant 

charge is given by the liquid sight glass 
indication, the condenser delta T in relation 
to the refrigerant pressure tables (pressure-
temperature), the superheat and the sub-
cooling, etc. (if additional charge is deemed 
necessary, refer to section 8).

 •  

Compressor short cycling: The number of 
cycles shall never exceed 12 starts per hour.

12 – Maintenance

  Internal pressure and surface temperature 

are dangerous and may cause permanent injury. 
Maintenance operators and installers require 
appropriate skills and tools. Tubing temperature may 
exceed 100°C / 212°F and can cause severe burns.

 Ensure that periodic service inspections to 

ensure system reliability and as required by local 
regulations are performed.
To prevent system related compressor problems, 
following periodic maintenance is recommended:
 •  Verify that safety devices are operational and 

properly set.

  •   Ensure that the system is leak tight.
  •   Check the compressor current draw by reading 

one of the parameters via Modbus.

 •   Confirm that the system is operating in a way 

consistent with previous maintenance records 
and ambient conditions.

 •  Check that all electrical connections are still 

adequately fastened.

 

• 

 

Keep the compressor clean and verify 
the absence of rust and oxidation on the 
compressor shell, tubes and electrical 
connections.

 •  

Acid / moisture content in system and oil 
should be checked regularly.

13 - Warranty

Always transmit the model number and serial 
number with any claim filed regarding this 
product.
Use the fault memory of the frequency converter 
to recover the fault descriptions before initializing 

the system and even before shutting off the 
power. 
Variable speed drive model and serial number 
must also be transmitted with the claim.
The product warranty may be void in following 
cases:
  •   Absence of nameplate.
 •  External modifications; in particular, drilling, 

welding, broken feet and shock marks.

  •   Compressor opened or returned unsealed.
 •  Rust, water or leak detection dye inside the 

compressor.

 •   Use of a refrigerant or lubricant not approved 

by Danfoss.

  •   Any deviation from recommended instructions 

pertaining to installation, application or 
maintenance.

  •   Use in mobile applications.
  •   Use in explosive atmospheric environment.
  •   No model number or serial number transmitted 

with the warranty claim.