Single compressors
Electrical data, connections and wiring
Fuses
UL Compliant fuses
Recommended circuit breaker
UL
Non UL
IP20
Bussmann
Bussmann
Bussmann
Bussmann
Max fuse
CDS 803
Type RK5
Type RK1
Type J
Type T
Type G
Moeller type
3x200-240 V IP20
4 TR/VZH028
FRS-R-50
KTN-R50
JKS-50
JJN-50
50
PKZM4-50
5 TR/VZH035
FRS-R-50
KTN-R50
JKS-50
JJN-50
50
PKZM4-50
6.5 TR/VZH044
FRS-R-60
KTN-R60
JKS-60
JJN-60
60
PKZM4-63
3x380-480 V IP20
4 TR/VZH028
FRS-R-25
KTS-R25
JKS-25
JJS-25
25
PKZM4-25
5 TR/VZH035
FRS-R-25
KTS-R25
JKS-25
JJS-25
25
PKZM4-25
6.5 TR/VZH044
FRS-R-30
KTS-R30
JKS-30
JJS-30
30
PKZM4-50
Danfoss recommends using the fuses listed
below to protect service personnel and property
in case of component break-down in the
frequency converter.
For circuit breakers, Moeller types have been
tested and are recommended. Other types of
circuit breakers may be used provided they limit
the energy to a level equal to or lower than the
Moeller types.
18
FRCC.PC.034.A2.02
Application Guidelines