Bit 05, Not used:
Bit 05 is not used in the status word.
Bit 06, Trip lock:
Bit 06 =
’
0
’
means that the frequency converter
is not trip locked.
Bit 06 =
’
1
’
means that the frequency converter
is trip locked and it cannot be reset before the
mains supply has been removed. The trip can be
reset either with 24 V external control back up or
after the power is connected again.
Bit 07, No warning/warning:
Bit 07 =
’
0
’
means that there are no warnings.
Bit 07 =
’
1
’
means that a warning has occurred.
Bit 08, Speed
≠
ref/speed = ref.:
Bit 08 =
’
0
’
means that the motor is running, but that
the present speed is different from the preset speed
reference. It might, for example, be the case while the
speed is being ramped up/down during start/stop.
Bit 08 =
’
1
’
means that the motor
’
s present speed
is the same as the preset speed reference.
Bit 09, Local operation/serial communication control:
Bit 09 =
’
0
’
means that [STOP/RESET] is activated on
the control unit, or that
Local control
in parameter
002
Local/remote operation
is selected. It is
not possible to control the frequency converter
via serial communication.
Bit 09 =
’
1
’
means that it is possible to control the
frequency converter via serial communication.
Bit 10, Outside frequency range:
Bit 10 =
’
0
’
, if the output frequency has reached
the value in parameter 201
Output frequency
low limit
or parameter 202
Output frequency
high limit
. Bit 10 = "1" means that the output
frequency is within the defined limits.
Bit 11, Running/not running:
Bit 11 =
’
0
’
means that the motor is not running.
Bit 11 =
’
1
’
means that the frequency converter
has a start signal or that the output frequency
is greater than 0 Hz.
Bit 13, Voltage warning high/low:
Bit 13 =
’
0
’
means that there are no voltage warnings.
Bit 13 =
’
1
’
means that the DC voltage in the frequency
converter
’
s intermediate circuit is too low or too high.
Bit 14, Current limit:
Bit 14 =
’
0
’
means that the output current is less than
the value in parameter 221
Current Limit I
LIM
.
Bit 14 =
’
1
’
means that the output current is
greater than the value in parameter 221
Current
LimitI
LIM
and that the frequency converter will
trip after a set period of time.
Bit 15, Thermal warning:
Bit 15 =
’
0
’
means that there is no thermal warning.
Bit 15 =
’
1
’
means that the temperature limit has been
exceeded in either the motor, frequency converter or
from a thermistor that is connected to a digital input.
■
Control word according to Fieldbus Profile
To select
Profidrive
in the control word, parameter 512
Telegram Profile
must be set to
Profidrive
[0].
The control word is used to send commands
from a master (e.g. a PC) to a slave (frequency
converter). Master
⇒
Slave.
Bit
Bit = 0
Bit =1
00
OFF 1
ON 1
01
OFF 2
ON 2
02
OFF 3
ON 3
03
Coasting stop
04
Quick stop
05
Freeze outp. freq.
06
Ramp stop
Start
07
Reset
08
Bus jog 1
09
Bus jog 2
10
Data not valid
Data valid
11
Slow down
12
Catch-up
13
Select Setup (lsb)
14
Select Setup (msb)
15
Reversing
Bit 00-01-02, OFF1-2-3/ON1-2-3:
Bit 00-01-02 =
’
0
’
causes ramp stop, which uses the
ramp time in parameters 207/208 or 209/210.
If
Relay 123
is selected in parameter 323
Relay
output
, the output relay will be activated when
the output frequency is 0 Hz.
Bit 00-01-02 =
’
1
’
means that the frequency
converter can start the motor if the other
starting conditions are fulfilled.
Bit 03, Coasting stop:
See description under
Control word according
to FC protocol.