Holding registers
Register Number
Description
00001-00006
Reserved
00007
Last error code from an FC data object interface
00008
Reserved
00009
Parameter index*
00010-00990
000 parameter group (parameters 001 through 099)
01000-01990
100 parameter group (parameters 100 through 199)
02000-02990
200 parameter group (parameters 200 through 299)
03000-03990
300 parameter group (parameters 300 through 399)
04000-04990
400 parameter group (parameters 400 through 499)
...
...
49000-49990
4900 parameter group (parameters 4900 through 4999)
50000
Input data: Frequency converter control word register (CTW).
50010
Input data: Bus reference register (REF).
...
...
50200
Output data: Frequency converter status word register (STW).
50210
Output data: Frequency converter main actual value register (MAV).
Table 7.18
* Used to specify the index number to be used when
accessing an indexed parameter.
RS-485 Installation and Set...
VLT
®
Refrigeration Drive Design Guide
96
MG16G102 - VLT
®