5.2.20 Supported data types
Value
Data type
3
Integer16
4
Integer32
5
Unsigned8
6
Unsigned16
7
Unsigned32
9
Visible string
10
Octet string (byte string)
33
N2 (standardised value)
35
V2 (bit sequence)
44
Error
54
Time difference without date indication
Table 5.12 Supported Data Types
5.2.21 Value
The value field contains the parameter value of the
request. When the response is negative, the field contains
a corresponding error code. If the values consist of an odd
number of bytes, a zero byte is appended to maintain the
word structure of the telegrams.
For a positive partial response, the parameter value field
contains the following attributes:
Format=Data type or byte, word, double word
Number of values=Actual number of values
Value=Parameter value
For a negative partial response, the parameter value field
contains the following:
Format=Error (44H)
Number of values=1
Value=Error value=Error number
5.2.22 Error Codes for Drive Profile V3.0
When the parameter request is invalid, the frequency
converter returns a corresponding error code.
lists the full range of error codes.
Error
code
Meaning
Additional
Info
0x00
Unknown parameter
0
0x01
Parameter is read-only.
sub-index
0x02
Value out of range due to maximum/minimum
value.
sub-index
0x03
Wrong sub-index
sub-index
0x04
Parameter is no array.
0
0x05
Wrong data type (wrong data length)
0
0x06
This parameter may not be set, only reset.
sub-index
0x07
Descriptive element is read-only.
sub-index
0x09
No description available (only value).
0
0x0b
Process control not possible.
0
0x0f
No text array available (only value).
0
0x11
Not possible in current state.
0
0x14
Value out of range due to drive state/configu-
ration.
sub-index
0x15
Reply too long (more than 240 bytes).
0
Error
code
Meaning
Additional
Info
0x16
Wrong parameter address (unknown or
unsupported value for attribute, element,
parameter number or sub-index or illegal
combination)
0
0x17
Illegal format (for writing)
0
0x18
Value amount not consistent
0
0x65
Wrong axis: action not possible with this axis
-
0x66
Unknown service request
-
0x67
This service is not possible with multi parameter
access
-
0x68
Parameter value can not be read from bus.
-
Table 5.13 Error Codes for DP-V1 Parameter Requests
5.3 PCV Parameter Access
The PROFINET cyclical data exchange performs parameter
access via the PCV channel. The PCV channel forms part of
the PPOs described in
.
Use the PCV channel to read and write parameter values,
and read status for descriptive attributes of each
parameter.
5.3.1 PCA Handling
The PCA part of PPO types 1, 2 and 5 performs several
tasks. Using PCA, the master controls and supervises
parameters, and requests a response from the follower.
Then the follower responds to a request from the master.
Requests and responses
is a handshake procedure and
cannot be batched. Therefore, when the master sends out
a read/write request, it must wait for the response before
it sends a new request. The request or response data value
is limited to maximum 4 bytes (see RC characteristics in
), which implies that text strings are not
transferable. For further information, see
chapter 7 Application Examples
5.3.2 PCA - Parameter Characteristics
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
RC
SMP
PNU
Table 5.14 PCA - Parameter Characteristics
RC: Request/response characteristics (Range 0..15)
SMP: Spontaneous message (Not supported)
PNU : Parameter no. (Range 1..1999)
5.3.3 Request/Response Handling
The RC portion of the PCA word defines:
•
The requests issued from the master to the
follower.
•
Other portions of the PCV involved:
Parameter Access
Programming Guide
28
Danfoss A/S © Rev. 05/2014 All rights reserved.
MG37G102
5