2.10 Cage Clamp Connection Diagram
CAUTION
Refer to the Operating Instructions for VLT
®
AutomationDrive FC 302 and VLT
®
Decentral Drive FCD 302 to connect the
terminals.
Do not connect the VLT
®
OneGearDrive directly to the power supply.
shows the VLT
®
OneGearDrive DA09LA10 with terminal box in Y-connection and the connection to the
thermal protection.
130BD422.10
V1
W1
U1
U
V
W
PE
U
V
W
T1
T2
Illustration 2.6 Cage Clamp Connection Diagram
Description
Inverter output
Colour
Typical cross section
Maximum cross section
Motor winding
U
black
AWG 16/1.5 mm
2
AWG 14/2.5 mm
2
V
blue
W
brown
Protective Earth
PE
yellow/green
AWG 16/1.5 mm
2
AWG 14/2.5 mm
2
Temperature protection
1)
KTY 84-130
T1
white
AWG 20/0.75 mm
2
AWG 16/1.5 mm
2
T2
brown
Table 2.5 Cage Clamp Connections
1) When connected to VLT
®
AutomationDrive FC 302 and VLT
®
Decentral Drive FCD 302, use analog input terminal 54, KTY sensor 1. For
information about parameter setting and programming, refer to the corresponding operating instructions.
T1
KTY 84-130
VLT
®
AutomationDrive FC 302
1)
VLT
®
Decentral Drive FCD 302
1)
T2
KTY Sensor 1
Analog Input 54
Table 2.6 Connections T1 and T2
1) Only if connected
Installation
VLT
®
OneGearDrive Operating Instructions
12
MG75C302 - VLT
®
is a registered Danfoss trademark
2