Configuration
MCD USB Module Instructions
MI.17.C1.02 - VLT
®
is a registered Danfoss trademark
4
6.
Identify the USB Serial Port assignment by checking Control panel > System > Hardware >
Device Manager> Ports (COM & LPT).
N.B.!:
If the USB port is not shown, disconnect then reconnect the cable. If the problem
persists, restart your PC.
7.
Open WinMaster and change the Network Settings to:
Protocol:
AP Binary or AP ASCII
Baud rate:
9600
Serial Port:
Use the serial port number identified above
8.
Apply control voltage to the soft starter. Bring WinMaster on-line, then Search for Network
Starters.
N.B.!:
The starter may trip on Starter Comms while the Master is off-line. Reset the soft starter
and place the Master on-line.
N.B.!:
The drivers will configure the USB port that the module is connected to. You must use
the same physical USB port every time you connect the module to the PC.