Illustration 1.2 Frequency Converter with the Blind Cover
Mounting the remote LCP
1.
Drill the hole in the wall that holds the LCP. The hole
diameter: 24 mm
±
1 mm (1 in
±
0.04 in). To ensure
that the base plate adjoins the wall, drill the hole
perpendicular to the wall (
±
1
°
). The kit is suitable for
insulated walls 30–90 mm (1.2–3.5 in) thick and solid
walls 1–20 mm (0.04–0.8 in) thick.
2.
Install the base plate with the D-sub connector. Use
the gasket and 4 self-tapping screws to secure the
plate. See
Illustration 1.3
.
1
Gasket
2
Base plate
3
Screws
Illustration 1.3 Base Plate with D-sub Connector
3.
Put the nut on the D-sub connector and tighten it
with torque of 1.5 Nm (13 in-lb). Ensure that the base
plate and the nut are tight on both sides of the wall.
For very thin walls, the nut can also be turned 180
°
.
See
Illustration 1.4
and
Illustration 1.5
.
1
Nut
2
Gasket
Illustration 1.4 The Nut, Standard Position, for Thick/Insulated
Walls
Installation Instructions
Remote Mounting of LCP
VLT
®
HVAC Drive FC 102
MI05A202