Illustration 1.2 Frequency Converter with the Blind Cover

Mounting the remote LCP

1.

Drill the hole in the wall that holds the LCP. The hole
diameter: 24 mm 

±

1 mm (1 in 

±

0.04 in). To ensure

that the base plate adjoins the wall, drill the hole
perpendicular to the wall (

±

1

°

). The kit is suitable for

insulated walls 30–90 mm (1.2–3.5 in) thick and solid
walls 1–20 mm (0.04–0.8 in) thick.

2.

Install the base plate with the D-sub connector. Use
the gasket and 4 self-tapping screws to secure the
plate. See 

Illustration 1.3

.

1

Gasket

2

Base plate

3

Screws

Illustration 1.3 Base Plate with D-sub Connector

3.

Put the nut on the D-sub connector and tighten it
with torque of 1.5 Nm (13 in-lb). Ensure that the base
plate and the nut are tight on both sides of the wall.
For very thin walls, the nut can also be turned 180

°

.

See 

Illustration 1.4

 and 

Illustration 1.5

.

1

Nut

2

Gasket

Illustration 1.4 The Nut, Standard Position, for Thick/Insulated

Walls

Installation Instructions

Remote Mounting of LCP
VLT

®

 HVAC Drive FC 102

MI05A202

Danfoss A/S © 11/2017 All rights reserved.

3

Summary of Contents for VLT LCP 11

Page 1: ...about safety precautions for installation refer to the product specific operating guide WARNING DISCHARGE TIME The frequency converter contains DC link capacitors which can remain charged even when th...

Page 2: ...harge Time VLT HVAC Drive FC 102 Mechanical Installation NOTICE The guidelines in this instruction are applicable for a frequency converter in a standard configuration without any modifications Instal...

Page 3: ...Use the gasket and 4 self tapping screws to secure the plate See Illustration 1 3 1 Gasket 2 Base plate 3 Screws Illustration 1 3 Base Plate with D sub Connector 3 Put the nut on the D sub connector...

Page 4: ...6 and Illustration 1 7 Illustration 1 8 shows the base plate with the LCP 1 Rubber flap 2 Opening at the top of the cradle Illustration 1 6 Insert the Rubber Flap into the Opening Illustration 1 7 Rub...

Page 5: ...and then push it until it clicks The unit with this cover has rating IP54 See Illustration 1 9 and Illustration 1 10 Illustration 1 9 Connect the Lid with the Front Cover Illustration 1 10 Base Plate...

Page 6: ...rs on the blind cover and the LCP with the supplied cable See Illustration 1 11 Illustration 1 11 Remote Connection of the LCP Installation Instructions Remote Mounting of LCP VLT HVAC Drive FC 102 6...

Page 7: ...lights 4 Rings for locking the cover Illustration 1 13 Remote LCP with the Cover The On Warn and Alarm indicator lights are visible with the closed front cover Lights are visible at an angle up to 45...

Page 8: ...disassembly tool Illustration 1 14 Front Cover and Disassembly Tool Illustration 1 15 Front Cover with Padlock Installation Instructions Remote Mounting of LCP VLT HVAC Drive FC 102 8 Danfoss A S 11...

Page 9: ...gainst the wall to mark the hole locations The scale of the template is 1 1 Illustration 1 16 Drilling Template Scale of 1 1 Installation Instructions Remote Mounting of LCP VLT HVAC Drive FC 102 MI05...

Page 10: ...ucts already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the resp...

Reviews: