3.2.7 0-5* Copy / Save
Copy parameter settings between set-ups and to/from the LCP.
0-50 LCP Copy
Option:
Function:
[0] *
No copy
No function
[1]
All to LCP
Copies all parameters in all set-ups from the adjustable frequency drive memory to the LCP memory.
For service purposes, it is recommended to copy all parameters to the LCP after commissioning.
[2]
All from LCP
Copies all parameters in all set-ups from the LCP memory to the adjustable frequency drive memory.
[3]
Size indep. of LCP
Copies only the parameters that are independent of the motor size. The latter selection can be used
to program several adjustable frequency drives with the same function without disturbing motor
data which are already set.
This parameter cannot be adjusted while the motor is running.
0-51 Set-up Copy
Option:
Function:
[0] *
No copy
No function
[1]
Copy to set-up 1
Copies all parameters in the present Programming Set-up (defined in par.0-11
) to Set-up 1.
[2]
Copy to set-up 2
Copies all parameters in the present Programming Set-up (defined in par.0-11
) to Set-up 2.
[3]
Copy to set-up 3
Copies all parameters in the present Programming Set-up (defined in par.0-11
) to Set-up 3.
[4]
Copy to set-up 4
Copies all parameters in the present Programming Set-up (defined in par.0-11
) to Set-up 4.
[9]
Copy to all
Copies the parameters in the present set-up over to each of the Set-ups 1 to 4.
3.2.8 0-6* Password
Define password access to menus.
0-60 Main Menu Password
Range:
Function:
100 N/A*
[0 - 999 N/A]
Define the password for access to the main menu via the [Main Menu] key. If par.0-61
is set to
Full access
[0], this parameter will be ignored.
0-61 Access to Main Menu w/o Password
Option:
Function:
[0] *
Full access
Disables password defined in par.0-60
.
[1]
Read-only
Prevent unauthorized editing of main menu parameters.
[2]
No access
Prevent unauthorized viewing and editing of main menu parameters.
[16]
All: No access
If
Full access
[0] is selected then par.0-60
Access to Personal Menu w/o Pass-
will be ignored.
VLT
®
HVAC Drive Programming Guide
3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-15