0-02 Motor Speed Unit
Option:
Function:
This parameter cannot be adjusted while the motor is running.
The display showing depends on settings in par.0-02
. The default setting of par.0-02
depends on
which region of the world the adjustable frequency drive is supplied to, but can be re-programmed
as required.
NOTE!
Changing the
Motor Speed Unit
will reset certain parameters to their initial value.
It is recommended to select the motor speed unit first before modifying other
parameters.
[0]
RPM
Selects display of motor speed variables and parameters (i.e. references, feedbacks and limits) in
terms of motor speed (RPM).
[1] *
Hz
Selects display of motor speed variables and parameters (i.e., references, feedbacks and limits) in
terms of output frequency to the motor (Hz).
0-03 Regional Settings
Option:
Function:
This parameter cannot be adjusted while the motor is running.
The display showing depends on settings in par.0-02
. The default setting of par.0-02
depends on
which region of the world the adjustable frequency drive is supplied to but can be re-programmed
as required.
[0] *
International
Sets par.1-20
units to [kW] and the default value of par.1-23
[50 Hz].
[1]
North America
Sets par.1-21
units to HP and the default value of par.1-23
to
60 Hz.
The setting not used is made invisible.
0-04 Operating State at Power-up
Option:
Function:
Select the operating mode upon reconnection of the adjustable frequency drive to AC line voltage
after power-down when operating in hand (local) mode.
[0] *
Resume
Resumes operation of the adjustable frequency drive maintaining the same local reference and the
same start/stop condition (applied by [Hand On]/[Off] on the LCP or Hand Start via a digital input
as before the adjustable frequency drive was powered down.
[1]
Forced stop, ref=old
Uses saved reference [1] to stop the adjustable frequency drive but at the same time retain in
memory the local speed reference prior to power-down. After AC line voltage is reconnected and
after receiving a start command (using the LCP [Hand On] button or Hand Start command via a
digital input), the adjustable frequency drive restarts and operates at the retained speed reference.
VLT
®
HVAC Drive Programming Guide
3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-3