6-27 Terminal 54 Live Zero
Option:
Function:
This parameter makes it possible to disable the Live Zero monitoring. For example, this to be used
if the analog outputs are used as part of a de-central I/O system (e.g., when used not as part of
any adjustable frequency drive related control functions, but for feeding a building management
system with data).
[0]
Disabled
[1] *
Enabled
3.8.5 6-3* Analog Input 3 MCB 101
Parameter group for configuring the scale and limits for analog input 3 (X30/11) placed on option module MCB 101.
6-30 Terminal X30/11 Low Voltage
Range:
Function:
0.07 V*
[0.00 - par. 6-31 V]
Sets the analog input scaling value to correspond to the low reference/feedback value (set in par.
6-34
Term. X30/11 Low Ref./Feedb. Value
6-31 Terminal X30/11 High Voltage
Range:
Function:
10.00 V*
[par. 6-30 - 10.00 V]
Sets the analog input scaling value to correspond to the high reference/feedback value (set in par.
6-35
Term. X30/11 High Ref./Feedb. Value
6-34 Term. X30/11 Low Ref./Feedb. Value
Range:
Function:
0.000 N/A* [-999999.999 - 999999.999 N/A]
Sets the analog input scaling value to correspond to the low voltage value (set in par.6-30
).
6-35 Term. X30/11 High Ref./Feedb. Value
Range:
Function:
100.000 N/
A*
[-999999.999 - 999999.999 N/A]
Sets the analog input scaling value to correspond to the high voltage value (set in par.6-31
6-36 Term. X30/11 Filter Time Constant
Range:
Function:
0.001 s*
[0.001 - 10.000 s]
A 1
st
order digital low pass filter time constant for suppressing electrical noise on terminal X30/11.
Term. X30/11 Filter Time Constant
cannot be changed while the motor is running.
6-37 Term. X30/11 Live Zero
Option:
Function:
This parameter makes it possible to disable Live Zero monitoring. For example, this may be used if
the analog outputs are used as part of a decentral I/O system (e.g., when not part of any adjustable
frequency drive-related control functions, but feeding a building management system with data).
[0] *
Disabled
[1] *
Enabled