6-01 Live Zero Timeout Function
Option:
Function:
Select the timeout function. The function set in par.6-01
will be activated
if the input signal on terminal 53 or 54 is below 50% of the value in par.6-10
for a time period defined in par.6-00
. If several timeouts
occur simultaneously, the adjustable frequency drive prioritizes the timeout functions as follows:
1.
2.
The output frequency of the adjustable frequency drive can be:
•
[1] frozen at the present value
•
[2] overruled to stop
•
[3] overruled to jog speed
•
[4] overruled to max. speed
•
[5] overruled to stop with subsequent trip
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
6-02 Fire Mode Live Zero Timeout Function
Option:
Function:
The function set in par.6-01
will be activated if the input signal on analog
inputs is below 50% of the value defined in parameter group 6-1* to 6-6* "Terminal xx Low Current”
or “Terminal xx Low Voltage" for a time period defined in par.6-00
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
VLT
®
HVAC Drive Programming Guide
3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-81
3