3.1.5 Internal Floating Point (ADF)
NPA
Unit
Description
Range
FC Par. Number
0
-
Max value of custom readout
0-32
1
-
Min value of custom readout
0-31
13
A
Motor Current(I
M.N
)
1-24
14
RPM
Motor nom. Speed
1-25
16
%
Resonance damping
1-64
18
Sec
Start delay
1-71
19
%
Preheat DC-current
2-00
20
%
DC brake current
2-01
21
Sec
DC braking time
2-02
22
Hz
DC brake cut-in frequency
2-03
29
-
Max output Frequency
4-19
34
Sec
Ramp Up Time
3-41
35
Sec
Ramp Down Time
3-42
36
Hz
Jog Frequency
3-11
37
%
Digital Reference 1
3-10:0
38
%
Digital Reference 2
3-10:1
39
%
Digital Reference 3
3-10:2
40
%
Digital Reference 4
3-10:3
41
A
Current Limit
4-18
42
Hz
Frequency 1. Bypass start
4-61:0
43
Hz
Frequency 1. Bypass stop
4-63:0
44
Hz
Frequency 2. Bypass start
4-61:1
45
Hz
Frequency 2. Bypass stop
4-63:1
46
Hz
Frequency 3. Bypass start
4-61:2
47
A
Frequency 3. Bypass stop
4-63:2
48
A
Frequency 4. Bypass start
4-61:3
49
Hz
Frequency 4. Bypass stop
4-63:3
50
A
Warning Current Low(I
LOW
)
4-50
51
A
Warning Current High (I
HIGH
)
4-51
52
Hz
Warning Freq. Low(F
LOW
)
4-52
53
Hz
Warning Freq. High(F
HIGH
)
4-53
54
Unit
Warning Low Ref.(Ref
LOW
)
4-54
55
Unit
Warning High Ref.(Ref
HIGH
)
4-55
56
Unit
Warning Low FB.(FB
LOW
)
4-56
57
Unit
Warning High FB.(FB
HIGH
)
4-57
60
V
Terminal 53 min scale V
6-10
61
V
Terminal 53 max scale V
6-11
62
V
Terminal 53 min scale mA
6-12
63
V
Terminal 53 max scale mA
6-13
64
A
Terminal 54 min. scale V
6-20
65
V
Terminal 54 max. scale V
6-21
66
V
Terminal 54 min. scale mA
6-22
67
A
Terminal 54 max. scale mA
6-23
68
Hz
Terminal 42 output puls scale
5-62
69
Hz
Terminal 45 output puls scale
5-65
70
mSec
CC Relay 1 ON Delay
5-41:0
71
mSec
CC Relay 1 ON Delay
5-42:0
72
mSec
CC Relay 1 ON Delay
5-41:1
73
Sec
CC Relay 1 ON Delay
5-42:1
Appendix
VLT
®
Metasys
MG.11.G2.02 - VLT
®
is a registered Danfoss trademark
25
3
3