3.8.2 6-1* Analog Input 1
Parameters for configuring the scaling and limits for analog
input 1 (terminal 53).
6-10 Terminal 53 Low Voltage
Range:
Function:
0.07 V
*
[ 0 - par.
6-11 V]
Enter the low-voltage value. This analog
input scaling value should correspond to
the low reference/feedback value set in
parameter 6-14 Terminal 53 Low Ref./Feedb.
Value
.
6-11 Terminal 53 High Voltage
Range:
Function:
10 V
*
[ par. 6-10
- 10 V]
Enter the high-voltage value. This analog
input scaling value should correspond to the
high reference/feedback value set in
parameter 6-15 Terminal 53 High Ref./Feedb.
Value
6-12 Terminal 53 Low Current
Range:
Function:
4 mA
*
[ 0 -
par. 6-13
mA]
Enter the low current value. This reference
signal should correspond to the low reference/
feedback value, set in
. Set the value at >2
mA to activate the live zero timeout function
in
parameter 6-01 Live Zero Timeout Function
6-13 Terminal 53 High Current
Range:
Function:
20 mA
*
[ par. 6-12 -
20 mA]
Enter the high current value
corresponding to the high reference/
feedback set in
.
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
Function:
0
*
[-999999.999 -
999999.999 ]
Enter the analog input scaling value that
corresponds to the low voltage/low
current set in
and
.
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Function:
Size
related
*
[-999999.999 -
999999.999 ]
Enter the analog input scaling
value that corresponds to the high
voltage/high current value set in
parameter 6-11 Terminal 53 High
Voltage
and
parameter 6-13 Terminal 53 High
Current
6-16 Terminal 53 Filter Time Constant
Range:
Function:
0.001 s
*
[0.001 - 10
s]
NOTICE
This parameter cannot be adjusted
while the motor is running.
Enter the filter time constant. This
constant is a first-order digital low-pass
filter time for suppressing electrical noise
in terminal 53. A high value improves
dampening, but also increases the delay
through the filter.
6-17 Terminal 53 Live Zero
Option:
Function:
Disables the live zero monitoring, for example if
the analog outputs are used as part of a
decentral I/O system (that is if these are used to
feed a building management system with data,
and not as part of any control functions related
to the frequency converter).
[0]
Disabled
[1]
*
Enabled
3.8.3 6-2* Analog Input 2
Parameters for configuring the scaling and limits for analog
input 2 (terminal 54).
6-20 Terminal 54 Low Voltage
Range:
Function:
0.07 V
*
[ 0 - par.
6-21 V]
Enter the low-voltage value. This analog
input scaling value should correspond to
the low reference/feedback value, set in
parameter 6-24 Terminal 54 Low Ref./Feedb.
Value
6-21 Terminal 54 High Voltage
Range:
Function:
10 V
*
[ par. 6-20
- 10 V]
Enter the high-voltage value. This analog
input scaling value should correspond to the
high reference/feedback value set in
parameter 6-25 Terminal 54 High Ref./Feedb.
Value
.
6-22 Terminal 54 Low Current
Range:
Function:
4 mA
*
[ 0 -
par. 6-23
mA]
Enter the low current value. This reference
signal should correspond to the low reference/
feedback value, set in
. Set the value at >2
mA to activate the live zero timeout function
in
parameter 6-01 Live Zero Timeout Function
.
Parameter Descriptions
Programming Guide
MG11CE02
Danfoss A/S © 03/2015 All rights reserved.
83