2-16 AC brake Max. Current
Range:
Function:
100 %
*
[ 0 - 1000.0
%]
NOTICE
Parameter 2-16 AC brake Max.
Current
does not have effect when
parameter 1-10 Motor
Construction
=[1] PM, non-salient
SPM.
Enter the maximum permissible current
when using AC brake to avoid
overheating of motor windings.
2-17 Over-voltage Control
Over voltage control (OVC) reduces the risk of the frequency
converter tripping due to an over voltage on the DC link caused
by generative power from the load.
Option:
Function:
NOTICE
The ramp time is automatically adjusted to
avoid tripping of the frequency converter.
[0]
Disabled No OVC required.
[2]
*
Enabled Activates OVC.