3.15 Parameters: 15-** Main Menu - Drive
Information
Parameter group containing frequency converter
information such as operating data, hardware configu-
ration, and software versions.
3.15.1 15-0* Operating Data
15-00 Operating hours
Range:
Function:
0 h
*
[0 - 2147483647 h] View how many hours the frequency
converter has run. The value is saved
when the frequency converter is
turned off.
15-01 Running Hours
Range:
Function:
0 h
*
[0 -
2147483647 h]
View how many hours the motor has run.
Reset the counter in
parameter 15-07 Reset Running Hours
Counter
. The value is saved when the
frequency converter is turned off.
15-02 kWh Counter
Range:
Function:
0 kWh
*
[0 -
2147483647
kWh]
Registers the power consumption of
the motor as a mean value over 1
hour. Reset the counter in
parameter 15-06 Reset kWh Counter
.
15-03 Power Up's
Range:
Function:
0
*
[0 - 2147483647 ] View the number of times the frequency
converter has been powered up.
15-04 Over Temp's
Range:
Function:
0
*
[0 - 65535 ] View the number of frequency converter
temperature faults, which have occurred.
15-05 Over Volt's
Range:
Function:
0
*
[0 - 65535 ] View the number of frequency converter
overvoltages, which have occurred.
15-06 Reset kWh Counter
Option:
Function:
[0]
*
Do not reset
NOTICE
The reset is carried out by pressing
[OK].
No reset of the kWh counter is desired.
15-06 Reset kWh Counter
Option:
Function:
[1]
Reset counter Press [OK] to reset the kWh counter to zero
(see
15-07 Reset Running Hours Counter
Option:
Function:
[0]
*
Do not
reset
No reset of the running hours counter is
desired.
[1]
Reset
counter
Select
[1] Reset counter
and press [OK] to reset
the running hours counter
(
) and
parameter 15-08 Number of Starts
to zero (see
also
15-08 Number of Starts
Range:
Function:
0
*
[0 - 2147483647 ] This is a readout parameter only. The
counter shows the number of starts and
stops caused by a normal Start/Stop
command and/or when entering/leaving
sleep mode.
3.15.2 15-1* Data Log Settings
The data log enables continuous logging of up to 4 data
sources (
parameter 15-10 Logging Source
) at individual rates
parameter 15-11 Logging Interval
). A trigger event
) and window
parameter 15-14 Samples Before Trigger
) are used to start
and stop the logging conditionally.
15-10 Logging Source
Array [4]
Option:
Function:
Select which variables are to
be logged.
[0]
*
None
[1397] Alert Alarm Word
[1398] Alert Warning Word
[1399] Alert Status Word
[1600] Control Word
[1601] Reference [Unit]
[1602] Reference [%]
[1603] Status Word
[1610] Power [kW]
[1611] Power [hp]
[1612] Motor Voltage
[1613] Frequency
[1614] Motor current
[1616] Torque [Nm]
[1617] Speed [RPM]
[1618] Motor Thermal
[1622] Torque [%]
Parameter Descriptions
VLT
®
HVAC Drive FC 102
124
Danfoss A/S © 03/2015 All rights reserved.
MG11CE02