4.1.21 Switches S201, S202 and S801
Use switches S201 (A53) and S202 (A54) to configure the
analog input terminals 53 and 54 as a current (0–20 mA)
or a voltage (-10 V to +10 V).
Enable termination on the RS-485 port (terminals 68 and
69) via the switch S801 (BUS TER.).
See
.
Default setting:
S201 (A53) = OFF (voltage input)
S202 (A54) = OFF (voltage input)
S801 (Bus termination) = OFF
NOTICE!
When changing the function of S201, S202, or S801, do
not to use force during the switch over. Remove the LCP
fixture (cradle) when operating the switches. Do not
operate the switches when the adjustable frequency
drive is powered.
130B
T310.11
Figure 4.26 Switch Location
4.2 Connection Examples
4.2.1 Start/Stop
Terminal 18 =
parameter 5-10 Terminal 18 Digital Input
[8]
Start
Terminal 27 =
parameter 5-12 Terminal 27 Digital Input
[0]
No operation
(Default
coast inverse
)
Terminal 37 = STO
Figure 4.27 Wiring Start/Stop
Electrical Installation
Instruction Manual
MG11F522
Danfoss A/S © 08/2014 All rights reserved.
61
4
4