130B
T312.10
Illustration 6.51 Insert Screwdriver
3.
Insert the cable in the adjacent circular hole.
130B
T311.10
Illustration 6.52 Insert Cable
4.
Remove the screwdriver. The cable is now
mounted to the terminal.
130B
T306.10
Illustration 6.53 Remove Screwdriver
To remove the cable from the terminal
1.
Insert a screwdriver
1)
in the square hole.
2.
Pull out the cable.
1)
Max. 0.4 x 2.5 mm
6.5.6 Basic Wiring Example
1.
Mount terminals from the accessory bag to the
front of the frequency converter.
2.
Connect terminals 18 and 27 to +24 V (terminal
12/13)
Default settings
18 = Start,
5-10 Terminal 18 Digital Input
[9]
27 = Stop inverse,
5-12 Terminal 27 Digital Input
[6]
37 = Safe Torque Off inverse
12
13
18
37
130BA156.12
32
27
19
29
33
20
P 5 - 12 [6]
P 5 - 10[9]
+24V
Speed
Start
Stop inverse
Safe Stop
Start (18)
Start (27)
Illustration 6.54 Basic Wiring
Electrical Installation
Design Guide
MG11BC02
Danfoss A/S © Rev. 06/2014 All rights reserved.
111
6
6