NOTE!
If one of the settings in parameter group 1-2* Motor Data
is changed, the advanced motor parameters,
to
, will return to default
setting.
This parameter cannot be adjusted while the motor is
running.
NOTE!
Full AMA should be run without filter only while reduced
AMA should be run with filter.
1-30 Stator Resistance (Rs)
Range:
Function:
Size related
*
[ 0.0 -
99.99 Ohm]
Set the stator resistance value. Enter
the value from a motor data sheet or
perform an AMA on a cold motor.
This parameter cannot be adjusted
while the motor is running.
1-33 Stator Leakage Reactance (X1)
Range:
Function:
Size related
*
[ 0.0 - 999.9 Ohm] Set stator leakage reactance of
motor.
Size related
*
[0.0–999.9 Ohm]
1-35 Main Reactance (Xh)
Range:
Function:
Size
related
*
[ 0.0 -
999.9
Ohm]
Set the main reactance of the motor using
one of these methods:
1.
Run an AMA on a cold motor. The
adjustable frequency drive will
measure the value from the
motor.
2.
Enter the X
h
value manually.
Obtain the value from the motor
supplier.
3.
Use the X
h
default setting. The
adjustable frequency drive
establishes the setting on the
basis of the motor nameplate
data.
NOTE!
This parameter cannot be adjusted while running.
1-37 d-axis Inductance (Ld)
Range:
Function:
Size related
*
[ 0 - 1000 ] Obtain the value from the permanent
magnet motor data sheet. The d-axis
inductance cannot be found by
performing an AMA.
1-39 Motor Poles
Range:
Function:
4
*
[2 -
100 ]
Enter the number of motor poles.
Poles ~n
n
@ 50 Hz
~n
n
@ 60 Hz
2
2,700–3,000
3,250–3,600
4
1,350–1,500
1,625–1,800
6
700–1,000
840–1,200
Table 3.3
The table shows the number of poles for normal
speed ranges of various motor types. Define
motors designed for other frequencies separately.
The motor pole value is always an even number,
because it refers to the total number of poles, not
pairs of poles.
This parameter cannot be adjusted while the
motor is running.
1-40 Back EMF at 1000 RPM
Range:
Function:
Size related
*
[ 10 - 9000 V] Line-Line RMS back EMF voltage at
1000 RPM
1-50 Motor Magnetisation at Zero Speed
Range:
Function:
100 %
*
[ 0 - 300.0 %]
1-52 Min Speed Normal Magnetising [Hz]
Range:
Function:
0 Hz
*
[ 0 - 10.0
Hz]
Set the required frequency for normal
magnetizing current.
Use this parameter along with
. See drawing
for
1-50 Motor Magnetisation at Zero Speed
1-55 U/f Characteristic - U
Range:
Function:
Size related
*
[0 - 999 V] Enter voltage at each frequency point
to manually form a U/f characteristic
matching motor. Frequency points are
defined in
Parameters
VLT
®
HVAC Basic Drive Programming Guide
3-10
MG18B222 - VLT
®
is a registered Danfoss trademark
3