In order to document immunity against electrical
interference from electrical phenomena, the following
immunity tests have been made on a system consisting of
a frequency converter (with options if relevant), a screened
control cable and a control box with potentiometer, motor
cable and motor.
The tests were performed in accordance with the following
basic standards:
•
EN 61000-4-2 (IEC 61000-4-2): Electrostatic
discharges (ESD): Simulation of electrostatic
discharges from human beings.
•
EN 61000-4-3 (IEC 61000-4-3): Incoming electro-
magnetic field radiation, amplitude modulated
simulation of the effects of radar and radio
communication equipment as well as mobile
communications equipment.
•
EN 61000-4-4 (IEC 61000-4-4): Burst transients:
Simulation of interference brought about by
switching a contactor, relay or similar devices.
•
EN 61000-4-5 (IEC 61000-4-5): Surge transients:
Simulation of transients brought about e.g. by
lightning that strikes near installations.
•
EN 61000-4-6 (IEC 61000-4-6): RF Common mode:
Simulation of the effect from radio-transmission
equipment joined by connection cables.
See
Voltage range: 200-240 V, 380-480 V
Basic standard
Burst
IEC 61000-4-4
Surge
IEC 61000-4-5
ESD
IEC
61000-4-2
Radiated electromagnetic
field
IEC 61000-4-3
RF common
mode voltage
IEC 61000-4-6
Acceptance criterion
B
B
B
A
A
Line
4 kV CM
2 kV/2
Ω
DM
4kV/12
Ω
CM
—
—
10 V
RMS
Motor
4 kV CM
4 kV/2
Ω
1)
—
—
10 V
RMS
Brake
4 kV CM
4 kV/2
Ω
1)
—
—
10 V
RMS
Load sharing
4 kV CM
4 kV/2
Ω
1)
—
—
10 V
RMS
Control wires
2 kV CM
2 kV/2
Ω
1)
—
—
10 V
RMS
Standard bus
2 kV CM
2 kV/2
Ω
1)
—
—
10 V
RMS
Relay wires
2 kV CM
2 kV/2
Ω
1)
—
—
10 V
RMS
Application and Fieldbus
options
2 kV CM
2 kV/2
Ω
1)
—
—
10 V
RMS
LCP cable
2 kV CM
2 kV/2
Ω
1)
—
—
10 V
RMS
External 24 V DC
2 V CM
0.5 kV/2
Ω
DM
1 kV/12 Ω CM
—
—
10 V
RMS
Enclosure
—
—
8 kV AD
6 kV CD
10 V/m
—
Table 2.5 EMC Immunity
1) Injection on cable shield
AD: Air Discharge
CD: Contact Discharge
CM: Common Mode
DM: Differential Mode
Product Overview
VLT
®
Decentral Drive FCD 302
16
MG04H102 - VLT
®
is a registered Danfoss trademark