RFI filter type
Conducted emission
Radiated emission
Standards and
requirements
EN 55011
Class B
Class A Group 1
Class A Group 2
Class B
Class A Group 1
Housing, trades
and light
industries
Industrial
environment
Industrial
environment
Housing, trades
and light
industries
Industrial
environment
EN/IEC 61800-3
Category C1
Category C2
Category C3
Category C1
Category C2
First
environment
Home and
office
First environment
Home and office
Second environment
Industrial
First environment
Home and office
First
environment
Home and office
H1
FCD302
0.37-3 kW
No
10 m
10 m
No
Yes
Table 2.2 EMC Test Results (Emission, Immunity)
2.2.3 Emission Requirements
According to the EMC product standard for adjustable
speed frequency converters EN/IEC 61800-3:2004 the EMC
requirements depend on the intended use of the
frequency converter. Four categories are defined in the
EMC product standard. The definitions of the 4 categories
together with the requirements for mains supply voltage
conducted emissions are given in
.
Category
Definition
Conducted emission requirement
according to the limits given in EN
55011
C1
Frequency converters installed in the first environment (home and office) with a
supply voltage less than 1000 V.
Class B
C2
Frequency converters installed in the first environment (home and office) with a
supply voltage less than 1000 V, which are neither plug-in nor movable and are
intended to be installed and commissioned by a professional.
Class A Group 1
C3
Frequency converters installed in the second environment (industrial) with a supply
voltage lower than 1000 V.
Class A Group 2
C4
Frequency converters installed in the second environment with a supply voltage
equal to or above 1000 V or rated current equal to or above 400 A or intended for
use in complex systems.
No limit line.
An EMC plan should be made.
Table 2.3 Emission Requirements
When the generic emission standards are used the
frequency converters are required to comply with the
limits in
Environment
Generic standard
Conducted emission requirement
according to the limits given in EN 55011
First environment
(home and office)
EN/IEC 61000-6-3 Emission standard for residential, commercial
and light industrial environments.
Class B
Second environment
(industrial environment)
EN/IEC 61000-6-4 Emission standard for industrial environments.
Class A Group 1
Table 2.4 Emission Limit Classes
2.2.4 Immunity Requirements
The immunity requirements for frequency converters
depend on the environment where they are installed. The
requirements for the industrial environment are higher
than the requirements for the home and office
environment. All Danfoss frequency converters comply
with the requirements for the industrial environment and
consequently comply also with the lower requirements for
home and office environment with a large safety margin.
Product Overview
VLT
®
Decentral Drive FCD 302
MG04H102 - VLT
®
is a registered Danfoss trademark
15