Refer to the three pins as 1, 2, and 3, reading bottom to top. Pins 1 and 2 of each connector are in parallel with the gate
drive signal sent to the IGBTs. Pin 1 is the signal and pin 2 is common.
1.
Turn on the split bus power supply (only 650 V).
2.
In stop mode, measure pins 1 and 2 of each test connector. A correct reading reading is approximately -9 V DC
which indicates that all IGBTs have been turned off.
3.
Apply the run command to the adjustable frequency drive and 30 Hz reference.
4.
If using a voltmeter, measure pins 1 and 2 of each connector. Waveform to IGBTs is a square wave that goes
positive to 14 V DC and negative to -9 V DC. Average voltage read by the voltmeter is 2.2 to 2.5 V DC.