8-50 Coasting Select
Option:
Function:
[2]
Logic AND Activates Start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
[3]
*
Logic OR
Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
8-52 DC Brake Select
Option:
Function:
Select control of the DC brake via the terminals
(digital input) and/or via the fieldbus.
NOTE
Only selection
[0] Digital input
is available
when
is set to
[1]
PM non-salient SPM
.
[0]
Digital
input
Activates Start command via a digital input.
[1]
Bus
Activates Start command via the serial
communication port or fieldbus option.
[2]
Logic AND Activates Start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
[3]
*
Logic OR
Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
8-53 Start Select
Option:
Function:
Select control of the frequency converter start
function via the terminals (digital input) and/or
via the fieldbus.
[0]
Digital
input
Activates Start command via a digital input.
[1]
Bus
Activates Start command via the serial
communication port or fieldbus option.
[2]
Logic AND Activates Start command via the fieldbus/serial
communication port, AND additionally via one
of the digital inputs.
[3]
*
Logic OR
Activates Start command via the fieldbus/serial
communication port OR via one of the digital
inputs.
8-54 Reversing Select
Option:
Function:
Select control of the frequency converter
reverse function via the terminals (digital
input) and/or via the fieldbus.
[0]
*
Digital
input
Activates Reverse command via a digital input.
8-54 Reversing Select
Option:
Function:
[1]
Bus
Activates Reverse command via the serial
communication port or fieldbus option.
[2]
Logic AND Activates Reverse command via the fieldbus/
serial communication port, AND additionally
via one of the digital inputs.
[3]
Logic OR
Activates Reverse command via the fieldbus/
serial communication port OR via one of the
digital inputs.
NOTE
This parameter is active only when
is set
to
[0] Digital and control word
.
8-55 Set-up Select
Option:
Function:
Select control of the frequency converter set-
up selection via the terminals (digital input)
and/or via the fieldbus.
[0]
Digital
input
Activates the set-up selection via a digital
input.
[1]
Bus
Activates the set-up selection via the serial
communication port or fieldbus option.
[2]
Logic AND Activates the set-up selection via the fieldbus/
serial communication port, AND additionally
via one of the digital inputs.
[3]
*
Logic OR
Activate the set-up selection via the fieldbus/
serial communication port OR via one of the
digital inputs.
8-56 Preset Reference Select
Option:
Function:
Select control of the frequency converter
Preset Reference selection via the terminals
(digital input) and/or via the fieldbus.
[0]
Digital
input
Activates Preset Reference selection via a
digital input.
[1]
Bus
Activates Preset Reference selection via the
serial communication port or fieldbus option.
[2]
Logic AND Activates Preset Reference selection via the
fieldbus/serial communication port, AND
additionally via one of the digital inputs.
[3]
*
Logic OR
Activates the Preset Reference selection via the
fieldbus/serial communication port OR via one
of the digital inputs.