Type designation
P11K
P15K
P18K
P22K
P30K
P37K
P45K
P55K
P75K
P90K
Overload
1)
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
Typical shaft output
[kW]
11
15
18.5
22
30
37
45
55
75
90
IP20/chassis
B3
B3
B3
B4
B4
B4
C3
C3
C4
C4
IP21/NEMA 1
B1
B1
B1
B2
B2
C1
C1
C1
C2
C2
IP55/NEMA 12
B1
B1
B1
B2
B2
C1
C1
C1
C2
C2
IP66/NEMA 4X
B1
B1
B1
B2
B2
C1
C1
C1
C2
C2
Output current
Continuous (3x525–550
V) [A]
19
23
28
36
43
54
65
87
105
137
Intermittent (3x525–550
V) [A]
21
25
31
40
47
59
72
96
116
151
Continuous (3x525–600
V) [A]
18
22
27
34
41
52
62
83
100
131
Intermittent (3x525–600
V) [A]
20
24
30
37
45
57
68
91
110
144
Continuous kVA (525 V
AC) [kVA]
18.1
21.9
26.7
34.3
41
51.4
61.9
82.9
100
130.5
Continuous kVA (575 V
AC) [kVA]
17.9
21.9
26.9
33.9
40.8
51.8
61.7
82.7
99.6
130.5
Maximum input current
Continuous (3x525–600
V) [A]
17.2
20.9
25.4
32.7
39
49
59
78.9
95.3
124.3
Intermittent (3x525–600
V) [A]
19
23
28
36
43
54
65
87
105
137
More specifications
Estimated power loss
3)
at rated maximum load
[W]
4)
300
400
475
525
700
750
850
1100
1400
1500
IP21, IP55, IP66
maximum cable cross-
section
2)
(mains, brake,
and load sharing) [mm
2
/
(AWG)]
16, 10, 10 (6, 8, 8)
35, –, – (2, –, –)
50, –, – (1, –, –)
150 (300 MCM)
IP21, IP55, IP66
maximum cable cross-
section
2)
(motor) [mm
2
/
(AWG)]
10, 10, – (8, 8, –)
35, 25, 25 (2, 4, 4)
50, –, – (1, –, –)
150 (300 MCM)
IP20 maximum cable
cross-section
2)
(mains,
brake, and load sharing)
[mm
2
/(AWG)]
10, 10, – (8, 8, –)
35, –, – (2, –, –)
50, –, – (1, –, –)
150 (300 MCM)
Maximum cable cross-
section
2)
with
disconnect
16, 10, 10 (6, 8, 8)
50, 35, 35 (1, 2, 2)
95, 70, 70
(3/0, 2/0,
2/0)
185, 150, 120
(350 MCM, 300
MCM, 4/0)
Efficiency
5)
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
Table 7.6 Mains Supply 3x525–600 V AC
For type of fuse, see chapter 7.8 Fuses and Circuit Breakers.
1) Normal overload 110% torque for a duration of 60 s.
2) The 3 values for the maximum cable cross-section are for single core, flexible wire, and flexible wire with sleeve, respectively.
3) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may
increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/
vltenergyefficiency.
Specifications
VLT
®
Refrigeration Drive FC 103
120
Danfoss A/S © 08/2015 All rights reserved.
MG16G202
7