4.12 Main Menu - Drive Information - Group
15
Parameter group containing frequency converter
information such as operating data, hardware configu-
ration, and software versions.
4.12.1 15-0* Operating Data
15-00 Operating hours
Range:
Function:
0 h
*
[0 - 0x7fffffff. h] View how many hours the frequency
converter has run. The value is saved
when the frequency converter is turned
off.
15-01 Running Hours
Range:
Function:
0 h
*
[0 -
0x7fffffff. h]
View how many hours the motor has run.
Reset the counter in
parameter 15-07 Reset
Running Hours Counter
. The value is saved
when the frequency converter is turned off.
15-02 kWh Counter
Range:
Function:
0 kWh
*
[0 -
2147483647
kWh]
View the output power of the
frequency converter in kWh as an
average value over 1 hour. Reset the
counter in
15-03 Power Up's
Range:
Function:
0
*
[0 - 2147483647 ] View the number of times the frequency
converter has been powered up.
15-04 Over Temp's
Range:
Function:
0
*
[0 - 65535 ] View the number of frequency converter
temperature faults that have occurred.
15-05 Over Volt's
Range:
Function:
0
*
[0 - 65535 ] View the number of frequency converter
overvoltages that have occurred.
15-06 Reset kWh Counter
Option:
Function:
NOTICE
To reset, press [OK] .
[0]
*
Do not reset
15-06 Reset kWh Counter
Option:
Function:
[1]
Reset counter To reset the kWh counter to 0, select
[1]
Reset
and press [OK] (see
parameter 15-02 kWh Counter
).
15-07 Reset Running Hours Counter
Option:
Function:
[0]
*
Do not
reset
[1]
Reset
counter
To reset the running hours counter to 0, select
[1] Reset
and press [OK] (see
parameter 15-01 Running Hours
). This
parameter cannot be selected via the serial
port, RS485.
Select
[0] Do not reset
if no reset of the
running-hours counter is required.
4.12.2 15-3* Alarm Log
Parameters in this group are array parameters, where up to
10 fault logs can be viewed. [0] is the most recent logged
data, and [9] the oldest. Fault codes, values, and time
stamp can be viewed for all logged data.
15-30 Alarm Log: Error Code
Range:
Function:
0
*
[0 - 255 ] View the fault code and look up its meaning in
chapter 5 Diagnostics and Troubleshooting
.
15-31 InternalFaultReason
Range:
Function:
0
*
[-32767 - 32767 ] View a description of the error. This
parameter is used with
alarm 38, Internal
fault
.
4.12.3 15-4* Drive Identification
Parameters containing read-only information about the
hardware and software configuration of the frequency
converter.
15-40 FC Type
Range:
Function:
0
*
[0 - 6 ] View the FC type code. The readout is identical to
the frequency converter series power field of the
type code definition, characters 1–6.
15-41 Power Section
Range:
Function:
0
*
[0 - 20 ] View the FC type code. The readout is identical to
the frequency converter series power field of the
type code definition, characters 7–10.
Parameters
Programming Guide
MG03N202
Danfoss A/S © 11/2015 All rights reserved.
93
4
4